Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Iowa State University
Assessment Year 2003
Principal Product Switch Gears
NAICS 335313 - Switchgear and Switchboard Apparatus Manufacturing
SIC 3613 - Switchgear And Switchboard Apparatus
Sales $100,000,000-$500,000,000
# of Employees 715
Plant Area (Sq.Ft.) 450,000
Annual Production 14,344 Pieces
Production Hrs. Annual 6,120
Location (State) IA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $329,970 13,511,400 kWh $0.02
Electricity Demand $161,229 29,604 kW-months/year $5.45
Natural Gas $292,190 60,094 MMBtu $4.86
TOTAL ENERGY COSTS $833,646
RECOMMENDED SAVINGS* $23,159 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $20,559
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$2,109
Cost:
$783
$1,462 60,657 $647 119 $1,462
60,657
kWh
$647
119
kW-months/year
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$511
Cost:
$34
$354 14,688 $157 29 $354
14,688
kWh
$157
29
kW-months/year
03: 2.4323 USE OPTIMUM SIZE AND CAPACITY EQUIPMENT Savings:
$1,475
Cost:
$570
$1,475 61,200 - - $1,475
61,200
kWh
-
-
kW-months/year
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$6,973
Cost:
$16,562
$4,832 200,494 $2,141 393 $4,832
200,494
kWh
$2,141
393
kW-months/year
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$11,303
Cost:
$4,835
$7,832 324,972 $3,471 637 $7,832
324,972
kWh
$3,471
637
kW-months/year
06: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$614
Cost:
$399
$614 25,459 - - $614
25,459
kWh
-
-
kW-months/year
07: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$174
Cost:
$514
$121 5,037 $53 10 $121
5,037
kWh
$53
10
kW-months/year
TOTAL RECOMMENDED Savings:
$23,159
Cost:
$23,697
$16,690 692,507 $6,469 1,188 $16,690
692,507
kWh
$6,469
1,188
kW-months/year
TOTAL IMPLEMENTED Savings:
$20,559
Cost:
$22,694
$14,247 591,160 $6,312 1,159 $14,247
591,160
kWh
$6,312
1,159
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand