IAC logo
IAC Assessment: IC0166
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: IC0166
IAC Center University of Illinois, Chicago
Assessment Year 2009
Principal Product Medical Instruments
NAICS 339112 - Surgical and Medical Instrument Manufacturing
SIC 3841 - Surgical And Medical Instruments
Sales $10,000,000-$50,000,000
# of Employees 170
Plant Area (Sq.Ft.) 67,000
Annual Production 234,293 Pieces
Production Hrs. Annual 4,216
Location (State) WI
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $112,624 2,130,240 kWh $0.05
Electricity Demand $63,440 4,879 kW-months/year $13.00
Natural Gas $8,530 764 MMBtu $11.16
TOTAL ENERGY COSTS $184,594
RECOMMENDED SAVINGS* $12,986 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $2,729
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Ancillary Material Cost One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Natural Gas Ancillary Material Cost One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ MMBtu $ $ $ $
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$2,511
Cost:
$10,994
$971 18,298 $663 51 - - $877 - - - $971
18,298
kWh
$663
51
kW-months/year
-
-
MMBtu
$877
-
$
-
-
$
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$3,135
Cost:
$4,045
$1,728 32,607 $1,469 113 - - $(-396) - $334 - $1,728
32,607
kWh
$1,469
113
kW-months/year
-
-
MMBtu
$(-396)
-
$
$334
-
$
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$757
Cost:
$136
$179 3,373 $130 10 - - $6 - $442 - $179
3,373
kWh
$130
10
kW-months/year
-
-
MMBtu
$6
-
$
$442
-
$
04: 2.7228 AVOID INTRODUCING HOT, HUMID, OR DIRTY AIR INTO HVAC SYSTEM Savings:
$2,442
Cost:
$1,720
$934 17,614 $1,508 116 - - - - - - $934
17,614
kWh
$1,508
116
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$84
Cost:
$345
$84 1,574 - - - - - - - - $84
1,574
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
06: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$134
Cost:
-
- - - - $134 12 - - - - -
-
kWh
-
-
kW-months/year
$134
12
MMBtu
-
-
$
-
-
$
07: 2.2692 USE OUTSIDE COLD WATER SOURCE AS A SUPPLY OF COOLING WATER Savings:
$3,264
Cost:
$16,200
$1,922 36,258 $1,342 103 - - - - - - $1,922
36,258
kWh
$1,342
103
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
08: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES Savings:
$659
Cost:
-
$191 3,600 $468 36 - - - - - - $191
3,600
kWh
$468
36
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
TOTAL RECOMMENDED Savings:
$12,986
Cost:
$33,440
$6,009 113,324 $5,580 429 $134 12 $487 - $776 - $6,009
113,324
kWh
$5,580
429
kW-months/year
$134
12
MMBtu
$487
-
$
$776
-
$
TOTAL IMPLEMENTED Savings:
$2,729
Cost:
$11,339
$1,055 19,872 $663 51 $134 12 $877 - - - $1,055
19,872
kWh
$663
51
kW-months/year
$134
12
MMBtu
$877
-
$
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $ $ $
Electricity Usage Electricity Demand Natural Gas Ancillary Material Cost One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Natural Gas Ancillary Material Cost One-time Revenue or Avoided Cost