Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Illinois, Chicago
Assessment Year 2019
Principal Product Steel Processing and Pickling of Master Coils
NAICS 423510 - Metal Service Centers and Other Metal Merchant Wholesalers
SIC 5051 - Metals Service Centers And Offices
Sales $100,000,000-$500,000,000
# of Employees 200
Plant Area (Sq.Ft.) 500,000
Annual Production 1,000,000 Tons
Production Hrs. Annual 6,200
Location (State) IN
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $545,342 9,089,040 kWh $0.06
Electricity Demand $359,494 28,284 kW-months/year $12.71
Natural Gas $334,474 68,680 MMBtu $4.87
TOTAL ENERGY COSTS $1,239,310
RECOMMENDED SAVINGS* $113,980 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $49,118
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$33,543
Cost:
$6,600
- - - - $33,543 6,888 -
-
kWh
-
-
kW-months/year
$33,543
6,888
MMBtu
02: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$2,588
Cost:
$1,928
$1,203 20,055 $1,385 109 - - $1,203
20,055
kWh
$1,385
109
kW-months/year
-
-
MMBtu
03: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,925
Cost:
$300
$1,713 27,415 $1,212 95 - - $1,713
27,415
kWh
$1,212
95
kW-months/year
-
-
MMBtu
04: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$62,274
Cost:
$210,000
$62,274 1,037,905 - - - - $62,274
1,037,905
kWh
-
-
kW-months/year
-
-
MMBtu
05: 3.6123 BURN WOOD BY-PRODUCTS FOR HEAT Savings:
$5,683
Cost:
$15,144
- - - - $5,683 1,167 -
-
kWh
-
-
kW-months/year
$5,683
1,167
MMBtu
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$6,967
Cost:
$7,769
$1,971 32,853 $4,996 393 - - $1,971
32,853
kWh
$4,996
393
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$113,980
Cost:
$241,741
$67,161 1,118,228 $7,592 598 $39,226 8,055 $67,161
1,118,228
kWh
$7,592
598
kW-months/year
$39,226
8,055
MMBtu
TOTAL IMPLEMENTED Savings:
$49,118
Cost:
$29,813
$3,684 60,268 $6,207 489 $39,226 8,055 $3,684
60,268
kWh
$6,207
489
kW-months/year
$39,226
8,055
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas