Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Illinois, Chicago
Assessment Year 2020
Principal Product Bottled Water Manufacturing
NAICS 312112 - Bottled Water Manufacturing
SIC 2086 - Bottled And Canned Soft Drinks
Sales $10,000,000-$50,000,000
# of Employees 35
Plant Area (Sq.Ft.) 200,000
Annual Production 205,000,000 Units
Production Hrs. Annual 8,736
Location (State) IN
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $473,357 6,762,240 kWh $0.07
Electricity Demand $191,969 15,053 kW-months/year $12.75
Electricity Fees $54,493 - $ -
Natural Gas $2,242 294 MMBtu $7.62
TOTAL ENERGY COSTS $722,061
RECOMMENDED SAVINGS* $59,013 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $46,952
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$15,040
Cost:
$26,145
- - $15,040 1,204 -
-
kWh
$15,040
1,204
kW-months/year
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$21,285
Cost:
$6,673
$16,619 237,409 $4,667 366 $16,619
237,409
kWh
$4,667
366
kW-months/year
03: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR Savings:
$5,211
Cost:
$50,440
$3,500 50,000 $1,711 134 $3,500
50,000
kWh
$1,711
134
kW-months/year
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$12,061
Cost:
$2,400
$12,061 172,298 - - $12,061
172,298
kWh
-
-
kW-months/year
05: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS Savings:
$5,416
Cost:
-
- - $5,416 425 -
-
kWh
$5,416
425
kW-months/year
TOTAL RECOMMENDED Savings:
$59,013
Cost:
$85,658
$32,179 459,707 $26,833 2,129 $32,179
459,707
kWh
$26,833
2,129
kW-months/year
TOTAL IMPLEMENTED Savings:
$46,952
Cost:
$83,258
$20,119 287,409 $26,833 2,129 $20,119
287,409
kWh
$26,833
2,129
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand