Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Univ. of Kansas |
---|---|
Assessment Year | 1995 |
Principal Product | animal feed |
NAICS | n/a |
SIC | 2047 - Dog And Cat Food |
Sales | $10,000,000-$50,000,000 |
# of Employees | 75 |
Plant Area (Sq.Ft.) | 89,000 |
Annual Production | 135,000 Tons |
Production Hrs. Annual | 6,000 |
Location (State) | KS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $307,411 | 5,323,271 | kWh | $0.06 |
Natural Gas | $227,830 | 69,438 | MMBtu | $3.28 |
TOTAL ENERGY COSTS | $549,727 | |||
RECOMMENDED SAVINGS* | $42,036 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $29,076 |
#|Description |
Savings Cost |
Status | Electricity Usage | Natural Gas | Water Disposal | Personnel Changes | Electricity Usage | Natural Gas | Water Disposal | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | MMBtu | $ | Tgal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $7,483 Cost: $13,216 |
$7,483 | 130,129 | - | - | - | - | - | - |
$7,483 130,129 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $8,072 Cost: $918 |
- | - | $8,072 | 2,461 | - | - | - | - |
- - kWh |
$8,072 2,461 MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $6,560 Cost: $300 |
- | - | $6,560 | 2,000 | - | - | - | - |
- - kWh |
$6,560 2,000 MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 3.4155 METER WASTE WATER |
Savings: $11,589 Cost: $5,000 |
- | - | - | - | $11,589 | - | - | - |
- - kWh |
- - MMBtu |
$11,589 - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,568 Cost: $3,155 |
$1,828 | 31,653 | - | - | - | - | $740 | - |
$1,828 31,653 kWh |
- - MMBtu |
- - Tgal |
$740 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $4,217 Cost: $2,780 |
$2,744 | 49,238 | - | - | - | - | $1,473 | - |
$2,744 49,238 kWh |
- - MMBtu |
- - Tgal |
$1,473 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $880 Cost: $650 |
$880 | 15,240 | - | - | - | - | - | - |
$880 15,240 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7132 INSTALL TIMERS ON LIGHT SWITCHES IN LITTLE USED AREAS |
Savings: $491 Cost: $90 |
$491 | 8,499 | - | - | - | - | - | - |
$491 8,499 kWh |
- - MMBtu |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $176 Cost: $240 |
$85 | 1,465 | - | - | - | - | $91 | - |
$85 1,465 kWh |
- - MMBtu |
- - Tgal |
$91 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $42,036 Cost: $26,349 |
$13,511 | 236,224 | $14,632 | 4,461 | $11,589 | - | $2,304 | - | $13,511 236,224 kWh |
$14,632 4,461 MMBtu |
$11,589 - Tgal |
$2,304 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $29,076 Cost: $20,609 |
$12,140 | 212,485 | $14,632 | 4,461 | - | - | $2,304 | - | $12,140 212,485 kWh |
$14,632 4,461 MMBtu |
- - Tgal |
$2,304 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | MMBtu | $ | Tgal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||