Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Lehigh University |
---|---|
Assessment Year | 2011 |
Principal Product | Food Flavors |
NAICS | 311942 - Spice and Extract Manufacturing |
SIC | 2087 - Flavoring Extracts And Syrups, Nec |
Sales | $100,000,000-$500,000,000 |
# of Employees | 64 |
Plant Area (Sq.Ft.) | 120,000 |
Annual Production | 6,000,000 Pounds |
Production Hrs. Annual | 8,760 |
Location (State) | PA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $176,710 | 2,771,113 | kWh | $0.06 |
Electricity Demand | $98,658 | 6,521 | kW-months/year | $15.13 |
Natural Gas | $181,973 | 47,265 | MMBtu | $3.85 |
TOTAL ENERGY COSTS | $457,341 | |||
RECOMMENDED SAVINGS* | $63,704 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $12,359 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $30,859 Cost: $30,000 |
$18,725 | 292,587 | $12,134 | 802 | - | - | - | - |
$18,725 292,587 kWh |
$12,134 802 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.9112 USE SOLAR HEAT TO HEAT WATER |
Savings: $11,446 Cost: $21,000 |
- | - | - | - | $11,446 | 2,973 | - | - |
- - kWh |
- - kW-months/year |
$11,446 2,973 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $8,384 Cost: $1,000 |
$5,343 | 83,478 | $3,041 | 201 | - | - | - | - |
$5,343 83,478 kWh |
$3,041 201 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $4,933 Cost: $3,000 |
- | - | $4,933 | 326 | - | - | - | - |
- - kWh |
$4,933 326 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $2,867 Cost: $192 |
$189 | 2,955 | $2,678 | 177 | - | - | - | - |
$189 2,955 kWh |
$2,678 177 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4112 INSTALL SOFT-START TO ELIMINATE NUISANCE TRIPS |
Savings: $2,360 Cost: $6,000 |
- | - | $2,360 | 156 | - | - | - | - |
- - kWh |
$2,360 156 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $1,240 Cost: $542 |
$1,013 | 15,825 | $227 | 15 | - | - | - | - |
$1,013 15,825 kWh |
$227 15 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $837 Cost: $2,921 |
$436 | 6,817 | $393 | 26 | - | - | $8 | - |
$436 6,817 kWh |
$393 26 kW-months/year |
- - MMBtu |
$8 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $778 Cost: - |
$596 | 9,316 | $182 | 12 | - | - | - | - |
$596 9,316 kWh |
$182 12 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $63,704 Cost: $64,655 |
$26,302 | 410,978 | $25,948 | 1,715 | $11,446 | 2,973 | $8 | - | $26,302 410,978 kWh |
$25,948 1,715 kW-months/year |
$11,446 2,973 MMBtu |
$8 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $12,359 Cost: $9,921 |
$6,375 | 99,611 | $5,976 | 395 | - | - | $8 | - | $6,375 99,611 kWh |
$5,976 395 kW-months/year |
- - MMBtu |
$8 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost |