Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Louisiana, Lafayette |
---|---|
Assessment Year | 2003 |
Principal Product | HFCs |
NAICS | 325998 - All Other Miscellaneous Chemical Product and Preparation Manufacturing |
SIC | 2819 - Industrial Inorganic Chemicals, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 120 |
Plant Area (Sq.Ft.) | 208,000 |
Annual Production | 39,000 Tons |
Production Hrs. Annual | 8,760 |
Location (State) | LA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $3,780,874 | 121,581,962 | kWh | $0.03 |
Electricity Demand | $2,301,415 | 208,089 | kW-months/year | $11.06 |
Electricity Fees | $313,319 | - | $ | - |
Natural Gas | $7,233,842 | 1,515,791 | MMBtu | $4.77 |
TOTAL ENERGY COSTS | $13,629,450 | |||
RECOMMENDED SAVINGS* | $588,896 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $246,886 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3321 USE STEAM PRESSURE REDUCTION TO GENERATE POWER |
Savings: $336,249 Cost: $481,633 |
$671,319 | 11,151,480 | - | - | - | - | $(-335,070) | (-52,560) | - | - |
$671,319 11,151,480 kWh |
- - kW-months/year |
- - $ |
$(-335,070) (-52,560) MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $217,796 Cost: $12,400 |
- | - | - | - | - | - | $217,796 | 34,164 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$217,796 34,164 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $19,066 Cost: $924 |
$8,609 | 276,827 | $9,523 | 861 | $934 | - | - | - | - | - |
$8,609 276,827 kWh |
$9,523 861 kW-months/year |
$934 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $5,635 Cost: $20 |
$3,368 | 108,296 | $1,991 | 180 | $276 | - | - | - | - | - |
$3,368 108,296 kWh |
$1,991 180 kW-months/year |
$276 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $4,821 Cost: $1,204 |
$1,897 | 60,985 | $2,688 | 243 | $236 | - | - | - | - | - |
$1,897 60,985 kWh |
$2,688 243 kW-months/year |
$236 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $4,389 Cost: $642 |
- | - | - | - | - | - | $4,389 | 662 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$4,389 662 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $940 Cost: $525 |
$319 | 10,249 | - | - | $16 | - | - | - | $605 | - |
$319 10,249 kWh |
- - kW-months/year |
$16 - $ |
- - MMBtu |
$605 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $588,896 Cost: $497,348 |
$685,512 | 11,607,837 | $14,202 | 1,284 | $1,462 | - | $(-112,885) | (-17,734) | $605 | - | $685,512 11,607,837 kWh |
$14,202 1,284 kW-months/year |
$1,462 - $ |
$(-112,885) (-17,734) MMBtu |
$605 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $246,886 Cost: $13,986 |
$11,977 | 385,123 | $11,514 | 1,041 | $1,210 | - | $222,185 | 34,826 | - | - | $11,977 385,123 kWh |
$11,514 1,041 kW-months/year |
$1,210 - $ |
$222,185 34,826 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes |