Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Louisiana, Lafayette |
---|---|
Assessment Year | 2004 |
Principal Product | Coffee |
NAICS | 311920 - Coffee and Tea Manufacturing |
SIC | 2095 - Roasted Coffee |
Sales | $50,000,000-$100,000,000 |
# of Employees | 58 |
Plant Area (Sq.Ft.) | 150,000 |
Annual Production | 20,000,000 Pounds |
Production Hrs. Annual | 2,600 |
Location (State) | LA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $137,239 | 2,726,400 | kWh | $0.05 |
Electricity Demand | $55,526 | 9,534 | kW-months/year | $5.82 |
Electricity Fees | $8,156 | - | $ | - |
Natural Gas | $115,409 | 14,357 | MMBtu | $8.04 |
TOTAL ENERGY COSTS | $316,330 | |||
RECOMMENDED SAVINGS* | $18,285 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $13,048 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $5,529 Cost: $100 |
$3,766 | 74,815 | $1,540 | 274 | $223 | - | - | - | - | - |
$3,766 74,815 kWh |
$1,540 274 kW-months/year |
$223 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $3,304 Cost: $2,261 |
- | - | - | - | - | - | $3,304 | 411 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$3,304 411 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $2,329 Cost: $430 |
$1,420 | 28,211 | $815 | 145 | $94 | - | - | - | - | - |
$1,420 28,211 kWh |
$815 145 kW-months/year |
$94 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,131 Cost: $2,120 |
$2,045 | 40,807 | - | - | $86 | - | - | - | - | - |
$2,045 40,807 kWh |
- - kW-months/year |
$86 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,933 Cost: $15 |
$1,152 | 22,878 | $703 | 125 | $78 | - | - | - | - | - |
$1,152 22,878 kWh |
$703 125 kW-months/year |
$78 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,325 Cost: $7,520 |
$811 | 16,110 | $461 | 82 | $53 | - | - | - | - | - |
$811 16,110 kWh |
$461 82 kW-months/year |
$53 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,160 Cost: $195 |
$1,113 | 22,116 | - | - | $47 | - | - | - | - | - |
$1,113 22,116 kWh |
- - kW-months/year |
$47 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $374 Cost: $180 |
$168 | 3,335 | $191 | 34 | $15 | - | - | - | - | - |
$168 3,335 kWh |
$191 34 kW-months/year |
$15 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $200 Cost: $140 |
$67 | 1,332 | $11 | 2 | $3 | - | - | - | $119 | - |
$67 1,332 kWh |
$11 2 kW-months/year |
$3 - $ |
- - MMBtu |
$119 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $18,285 Cost: $12,961 |
$10,542 | 209,604 | $3,721 | 662 | $599 | - | $3,304 | 411 | $119 | - | $10,542 209,604 kWh |
$3,721 662 kW-months/year |
$599 - $ |
$3,304 411 MMBtu |
$119 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $13,048 Cost: $10,685 |
$9,390 | 186,726 | $3,018 | 537 | $521 | - | - | - | $119 | - | $9,390 186,726 kWh |
$3,018 537 kW-months/year |
$521 - $ |
- - MMBtu |
$119 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Ancillary Material Cost |