Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Louisiana, Lafayette |
---|---|
Assessment Year | 2004 |
Principal Product | Printing |
NAICS | 323111 - Commercial Printing (except Screen and Books) |
SIC | 2732 - Book Printing |
Sales | $5,000,000-$10,000,000 |
# of Employees | 57 |
Plant Area (Sq.Ft.) | 44,000 |
Annual Production | 52,195,827 Pieces |
Production Hrs. Annual | 4,992 |
Location (State) | LA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $95,324 | 1,920,204 | kWh | $0.05 |
Electricity Demand | $32,479 | 5,446 | kW-months/year | $5.96 |
Electricity Fees | $12,636 | - | $ | - |
Natural Gas | $16,966 | 1,983 | MMBtu | $8.56 |
TOTAL ENERGY COSTS | $157,405 | |||
RECOMMENDED SAVINGS* | $23,352 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $18,645 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $11,409 Cost: $135 |
$10,381 | 209,116 | - | - | $1,028 | - | - | - |
$10,381 209,116 kWh |
- - kW-months/year |
$1,028 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $4,426 Cost: $1,560 |
$2,959 | 59,814 | $1,067 | 179 | $400 | - | - | - |
$2,959 59,814 kWh |
$1,067 179 kW-months/year |
$400 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.6232 INSTALL SET-BACK TIMERS |
Savings: $2,941 Cost: $18 |
$2,676 | 53,913 | - | - | $265 | - | - | - |
$2,676 53,913 kWh |
- - kW-months/year |
$265 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,103 Cost: $30 |
$748 | 15,067 | $256 | 43 | $99 | - | - | - |
$748 15,067 kWh |
$256 43 kW-months/year |
$99 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $870 Cost: $400 |
$792 | 15,962 | - | - | $78 | - | - | - |
$792 15,962 kWh |
- - kW-months/year |
$78 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $273 Cost: $300 |
$248 | 4,993 | - | - | $25 | - | - | - |
$248 4,993 kWh |
- - kW-months/year |
$25 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7132 INSTALL TIMERS ON LIGHT SWITCHES IN LITTLE USED AREAS |
Savings: $663 Cost: $96 |
$603 | 12,141 | - | - | $60 | - | - | - |
$603 12,141 kWh |
- - kW-months/year |
$60 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $167 Cost: $120 |
$152 | 3,065 | - | - | $15 | - | - | - |
$152 3,065 kWh |
- - kW-months/year |
$15 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 4.611 BEGIN A PRACTICE OF PREDICTIVE / PREVENTATIVE MAINTENANCE |
Savings: $1,500 Cost: $60 |
- | - | - | - | - | - | $1,500 | - |
- - kWh |
- - kW-months/year |
- - $ |
$1,500 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $23,352 Cost: $2,719 |
$18,559 | 374,071 | $1,323 | 222 | $1,970 | - | $1,500 | - | $18,559 374,071 kWh |
$1,323 222 kW-months/year |
$1,970 - $ |
$1,500 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $18,645 Cost: $2,575 |
$14,532 | 292,950 | $1,067 | 179 | $1,546 | - | $1,500 | - | $14,532 292,950 kWh |
$1,067 179 kW-months/year |
$1,546 - $ |
$1,500 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Ancillary Material Cost |