Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Louisiana, Lafayette |
---|---|
Assessment Year | 2004 |
Principal Product | Tubing |
NAICS | 331210 - Iron and Steel Pipe and Tube Manufacturing from Purchased Steel |
SIC | 3317 - Steel Pipe And Tubes |
Sales | $50,000,000-$100,000,000 |
# of Employees | 250 |
Plant Area (Sq.Ft.) | 700,000 |
Annual Production | 103,704 Tons |
Production Hrs. Annual | 6,240 |
Location (State) | AR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $716,301 | 26,695,820 | kWh | $0.03 |
Electricity Demand | $681,213 | 118,579 | kW-months/year | $5.74 |
Electricity Fees | $22,894 | - | $ | - |
Natural Gas | $363,250 | 55,369 | MMBtu | $6.56 |
TOTAL ENERGY COSTS | $1,783,658 | |||
RECOMMENDED SAVINGS* | $199,792 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $110,539 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $61,254 Cost: $2,590 |
$57,923 | 2,158,871 | $2,366 | 4,151 | $965 | - | - | - | - | - |
$57,923 2,158,871 kWh |
$2,366 4,151 kW-months/year |
$965 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $55,907 Cost: - |
- | - | $55,027 | 96,538 | $880 | - | - | - | - | - |
- - kWh |
$55,027 96,538 kW-months/year |
$880 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $41,577 Cost: $4,400 |
$40,922 | 1,525,251 | - | - | $655 | - | - | - | - | - |
$40,922 1,525,251 kWh |
- - kW-months/year |
$655 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $21,326 Cost: $420 |
$20,990 | 782,346 | - | - | $336 | - | - | - | - | - |
$20,990 782,346 kWh |
- - kW-months/year |
$336 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $7,708 Cost: $2,585 |
$7,587 | 287,613 | - | - | $121 | - | - | - | - | - |
$7,587 287,613 kWh |
- - kW-months/year |
$121 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $3,529 Cost: $720 |
$3,473 | 129,455 | - | - | $56 | - | - | - | - | - |
$3,473 129,455 kWh |
- - kW-months/year |
$56 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $2,881 Cost: $911 |
- | - | - | - | - | - | $2,881 | 439 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$2,881 439 MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 4.611 BEGIN A PRACTICE OF PREDICTIVE / PREVENTATIVE MAINTENANCE |
Savings: $5,610 Cost: $6,030 |
- | - | - | - | - | - | - | - | $5,610 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
$5,610 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $199,792 Cost: $17,656 |
$130,895 | 4,883,536 | $57,393 | 100,689 | $3,013 | - | $2,881 | 439 | $5,610 | - | $130,895 4,883,536 kWh |
$57,393 100,689 kW-months/year |
$3,013 - $ |
$2,881 439 MMBtu |
$5,610 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $110,539 Cost: $9,575 |
$106,432 | 3,971,735 | $2,366 | 4,151 | $1,741 | - | - | - | - | - | $106,432 3,971,735 kWh |
$2,366 4,151 kW-months/year |
$1,741 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes |