Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Louisiana, Lafayette |
---|---|
Assessment Year | 2004 |
Principal Product | ship and repair |
NAICS | 336611 - Ship Building and Repairing |
SIC | 3731 - Ship Building And Repairing |
Sales | $5,000,000-$10,000,000 |
# of Employees | 40 |
Plant Area (Sq.Ft.) | 60,000 |
Annual Production | 54 Pieces |
Production Hrs. Annual | 3,510 |
Location (State) | LA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $85,501 | 1,473,546 | kWh | $0.06 |
Electricity Demand | $25,765 | 8,441 | kW-months/year | $3.05 |
Electricity Fees | $3,815 | - | $ | - |
TOTAL ENERGY COSTS | $115,081 | |||
RECOMMENDED SAVINGS* | $16,461 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $9,428 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $4,929 Cost: $825 |
$3,805 | 65,578 | $972 | 168 | $152 | - | - | - | - | - |
$3,805 65,578 kWh |
$972 168 kW-months/year |
$152 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4324 REPLACE HYDRAULIC / PNEUMATIC EQUIPMENT WITH ELECTRIC EQUIPMENT |
Savings: $2,415 Cost: $895 |
$2,336 | 40,256 | - | - | $79 | - | - | - | - | - |
$2,336 40,256 kWh |
- - kW-months/year |
$79 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $899 Cost: $30 |
$869 | 14,976 | - | - | $30 | - | - | - | - | - |
$869 14,976 kWh |
- - kW-months/year |
$30 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $778 Cost: $990 |
$752 | 12,961 | - | - | $26 | - | - | - | - | - |
$752 12,961 kWh |
- - kW-months/year |
$26 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $755 Cost: $525 |
$290 | 4,993 | - | - | $10 | - | $455 | - | - | - |
$290 4,993 kWh |
- - kW-months/year |
$10 - $ |
$455 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $754 Cost: $1,120 |
$729 | 12,571 | - | - | $25 | - | - | - | - | - |
$729 12,571 kWh |
- - kW-months/year |
$25 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $261 Cost: $30 |
$252 | 4,342 | - | - | $9 | - | - | - | - | - |
$252 4,342 kWh |
- - kW-months/year |
$9 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $170 Cost: $270 |
$164 | 2,830 | - | - | $6 | - | - | - | - | - |
$164 2,830 kWh |
- - kW-months/year |
$6 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 4.611 BEGIN A PRACTICE OF PREDICTIVE / PREVENTATIVE MAINTENANCE |
Savings: $5,500 Cost: $1,050 |
- | - | - | - | - | - | $3,000 | - | $2,500 | - |
- - kWh |
- - kW-months/year |
- - $ |
$3,000 - $ |
$2,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $16,461 Cost: $5,735 |
$9,197 | 158,507 | $972 | 168 | $337 | - | $3,455 | - | $2,500 | - | $9,197 158,507 kWh |
$972 168 kW-months/year |
$337 - $ |
$3,455 - $ |
$2,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $9,428 Cost: $3,170 |
$8,155 | 140,553 | $972 | 168 | $301 | - | - | - | - | - | $8,155 140,553 kWh |
$972 168 kW-months/year |
$301 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost |