Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Louisiana, Lafayette |
---|---|
Assessment Year | 2006 |
Principal Product | Steel Joist and Gerters |
NAICS | 332312 - Fabricated Structural Metal Manufacturing |
SIC | 3441 - Fabricated Structural Metal |
Sales | $50,000,000-$100,000,000 |
# of Employees | 503 |
Plant Area (Sq.Ft.) | 193,430 |
Annual Production | 82,000 Tons |
Production Hrs. Annual | 4,992 |
Location (State) | AR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $286,277 | 6,316,280 | kWh | $0.05 |
Electricity Demand | $96,404 | 17,361 | kW-months/year | $5.55 |
Electricity Fees | $31,015 | - | $ | - |
Natural Gas | $92,512 | 8,388 | MMBtu | $11.03 |
TOTAL ENERGY COSTS | $506,208 | |||
RECOMMENDED SAVINGS* | $30,189 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $14,162 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 4.611 BEGIN A PRACTICE OF PREDICTIVE / PREVENTATIVE MAINTENANCE |
Savings: $11,704 Cost: $5,420 |
$3,075 | 67,891 | - | - | $249 | - | $6,880 | - | $1,500 | - |
$3,075 67,891 kWh |
- - kW-months/year |
$249 - $ |
$6,880 - $ |
$1,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 4.611 BEGIN A PRACTICE OF PREDICTIVE / PREVENTATIVE MAINTENANCE |
Savings: $7,890 Cost: $5,109 |
- | - | - | - | - | - | $7,890 | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$7,890 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $3,503 Cost: $3,652 |
$3,075 | 67,891 | - | - | $428 | - | - | - | - | - |
$3,075 67,891 kWh |
- - kW-months/year |
$428 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $3,127 Cost: $630 |
$2,893 | 63,860 | - | - | $234 | - | - | - | - | - |
$2,893 63,860 kWh |
- - kW-months/year |
$234 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,371 Cost: $600 |
$1,268 | 27,996 | - | - | $103 | - | - | - | - | - |
$1,268 27,996 kWh |
- - kW-months/year |
$103 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,087 Cost: $770 |
$332 | 7,323 | $56 | 10 | $31 | - | $668 | - | - | - |
$332 7,323 kWh |
$56 10 kW-months/year |
$31 - $ |
$668 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $756 Cost: $359 |
$560 | 12,369 | $139 | 25 | $57 | - | - | - | - | - |
$560 12,369 kWh |
$139 25 kW-months/year |
$57 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $751 Cost: $600 |
$695 | 15,352 | - | - | $56 | - | - | - | - | - |
$695 15,352 kWh |
- - kW-months/year |
$56 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $30,189 Cost: $17,140 |
$11,898 | 262,682 | $195 | 35 | $1,158 | - | $15,438 | - | $1,500 | - | $11,898 262,682 kWh |
$195 35 kW-months/year |
$1,158 - $ |
$15,438 - $ |
$1,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $14,162 Cost: $6,790 |
$4,675 | 103,210 | $56 | 10 | $383 | - | $7,548 | - | $1,500 | - | $4,675 103,210 kWh |
$56 10 kW-months/year |
$383 - $ |
$7,548 - $ |
$1,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||