Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Louisiana, Lafayette |
---|---|
Assessment Year | 2007 |
Principal Product | Aggregate |
NAICS | 327110 - Pottery, Ceramics, and Plumbing Fixture Manufacturing |
SIC | 3295 - Minerals, Ground Or Treated |
Sales | $10,000,000-$50,000,000 |
# of Employees | 42 |
Plant Area (Sq.Ft.) | 215,000 |
Annual Production | 500,000 Units |
Production Hrs. Annual | 8,736 |
Location (State) | LA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $880,405 | 9,400,800 | kWh | $0.09 |
Electricity Fees | $15,518 | - | $ | - |
Natural Gas | $107,699 | 9,602 | MMBtu | $11.22 |
Coal | $2,538,194 | 680,660 | MMBtu | $3.73 |
TOTAL ENERGY COSTS | $3,541,816 | |||
RECOMMENDED SAVINGS* | $1,159,616 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $1,151,055 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Fees | Coal | Electricity Usage | Electricity Fees | Coal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $818,045 Cost: $90,421 |
- | - | - | - | $818,045 | 219,315 |
- - kWh |
- - $ |
$818,045 219,315 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $243,412 Cost: $19,445 |
- | - | - | - | $243,412 | 65,258 |
- - kWh |
- - $ |
$243,412 65,258 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4222 INSTALL ADEQUATE DRYERS ON AIR LINES TO ELIMINATE BLOWDOWN |
Savings: $53,421 Cost: $607 |
$52,497 | 560,561 | $924 | - | - | - |
$52,497 560,561 kWh |
$924 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $22,045 Cost: $3,640 |
$21,664 | 231,330 | $381 | - | - | - |
$21,664 231,330 kWh |
$381 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $12,108 Cost: $780 |
$11,898 | 127,052 | $210 | - | - | - |
$11,898 127,052 kWh |
$210 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7132 INSTALL TIMERS ON LIGHT SWITCHES IN LITTLE USED AREAS |
Savings: $6,327 Cost: $450 |
$6,218 | 66,394 | $109 | - | - | - |
$6,218 66,394 kWh |
$109 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,490 Cost: $30 |
$1,464 | 15,632 | $26 | - | - | - |
$1,464 15,632 kWh |
$26 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $965 Cost: $240 |
$948 | 10,118 | $17 | - | - | - |
$948 10,118 kWh |
$17 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $667 Cost: $623 |
$655 | 6,989 | $12 | - | - | - |
$655 6,989 kWh |
$12 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $602 Cost: $1,379 |
$591 | 6,311 | $11 | - | - | - |
$591 6,311 kWh |
$11 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $534 Cost: $388 |
$525 | 5,604 | $9 | - | - | - |
$525 5,604 kWh |
$9 - $ |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $1,159,616 Cost: $118,003 |
$96,460 | 1,029,991 | $1,699 | - | $1,061,457 | 284,573 | $96,460 1,029,991 kWh |
$1,699 - $ |
$1,061,457 284,573 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $1,151,055 Cost: $115,311 |
$88,048 | 940,179 | $1,550 | - | $1,061,457 | 284,573 | $88,048 940,179 kWh |
$1,550 - $ |
$1,061,457 284,573 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Fees | Coal | Electricity Usage | Electricity Fees | Coal |