Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Louisiana, Lafayette |
---|---|
Assessment Year | 2009 |
Principal Product | Oil field tools |
NAICS | 332999 - All Other Miscellaneous Fabricated Metal Product Manufacturing |
SIC | 3499 - Fabricated Metal Products, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 142 |
Plant Area (Sq.Ft.) | 27,285 |
Annual Production | 360 Pieces |
Production Hrs. Annual | 2,400 |
Location (State) | LA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $85,418 | 867,000 | kWh | $0.10 |
Electricity Fees | $2,580 | - | $ | - |
Natural Gas | $21,831 | 1,322 | MMBtu | $16.51 |
TOTAL ENERGY COSTS | $109,829 | |||
RECOMMENDED SAVINGS* | $18,252 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $17,781 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Fees | Natural Gas | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Fees | Natural Gas | Personnel Changes | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | $ | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $8,673 Cost: $10,644 |
- | - | - | - | $8,673 | 525 | - | - | - | - |
- - kWh |
- - $ |
$8,673 525 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $4,439 Cost: $1,680 |
$4,310 | 43,744 | $129 | - | - | - | - | - | - | - |
$4,310 43,744 kWh |
$129 - $ |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $2,922 Cost: $180 |
$2,837 | 28,800 | $85 | - | - | - | - | - | - | - |
$2,837 28,800 kWh |
$85 - $ |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 4.611 BEGIN A PRACTICE OF PREDICTIVE / PREVENTATIVE MAINTENANCE |
Savings: $1,618 Cost: $120 |
$115 | 1,170 | $3 | - | - | - | - | - | $1,500 | - |
$115 1,170 kWh |
$3 - $ |
- - MMBtu |
- - $ |
$1,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $354 Cost: $312 |
$344 | 3,494 | $10 | - | - | - | - | - | - | - |
$344 3,494 kWh |
$10 - $ |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $117 Cost: $132 |
$114 | 1,152 | $3 | - | - | - | - | - | - | - |
$114 1,152 kWh |
$3 - $ |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $129 Cost: $70 |
$66 | 666 | $2 | - | - | - | $61 | - | - | - |
$66 666 kWh |
$2 - $ |
- - MMBtu |
$61 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $18,252 Cost: $13,138 |
$7,786 | 79,026 | $232 | - | $8,673 | 525 | $61 | - | $1,500 | - | $7,786 79,026 kWh |
$232 - $ |
$8,673 525 MMBtu |
$61 - $ |
$1,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $17,781 Cost: $12,694 |
$7,328 | 74,380 | $219 | - | $8,673 | 525 | $61 | - | $1,500 | - | $7,328 74,380 kWh |
$219 - $ |
$8,673 525 MMBtu |
$61 - $ |
$1,500 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | $ | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Fees | Natural Gas | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Fees | Natural Gas | Personnel Changes | One-time Revenue or Avoided Cost |