Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Loyola Marymount University |
---|---|
Assessment Year | 2001 |
Principal Product | opto-electronic components |
NAICS | n/a |
SIC | 3674 - Semiconductors And Related Devices |
Sales | $10,000,000-$50,000,000 |
# of Employees | 275 |
Plant Area (Sq.Ft.) | 42,000 |
Annual Production | 250,000 Pieces |
Production Hrs. Annual | 2,080 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $292,930 | 4,812,533 | kWh | $0.06 |
Electricity Demand | $120,994 | 10,405 | kW-months/year | $11.63 |
Electricity Fees | $37,930 | - | $ | - |
Natural Gas | $5,061 | 463 | MMBtu | $10.93 |
TOTAL ENERGY COSTS | $456,915 | |||
RECOMMENDED SAVINGS* | $475,942 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $6,110 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7145 INSTALL SKYLIGHTS |
Savings: $650 Cost: $1,600 |
$445 | 3,144 | $205 | 20 | - | - | - | - |
$445 3,144 kWh |
$205 20 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7144 INSTALL SPECTRAL REFLECTORS / DELAMP |
Savings: $3,603 Cost: $5,085 |
$2,691 | 20,877 | $912 | 102 | - | - | - | - |
$2,691 20,877 kWh |
$912 102 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $35,295 Cost: $60,000 |
$16,385 | 121,550 | $18,910 | 2,020 | - | - | - | - |
$16,385 121,550 kWh |
$18,910 2,020 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME |
Savings: $2,507 Cost: - |
$4,627 | 35,490 | $1,065 | 83 | $(-3,185) | - | - | - |
$4,627 35,490 kWh |
$1,065 83 kW-months/year |
$(-3,185) - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.8112 COMBINE UTILITY METERS |
Savings: $100,007 Cost: $60,200 |
- | - | - | - | - | - | $100,007 | - |
- - kWh |
- - kW-months/year |
- - $ |
$100,007 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 3.6193 INSTALL EQUIPMENT (eg COMPACTOR) TO REDUCE DISPOSAL COSTS |
Savings: $21,880 Cost: $11,800 |
- | - | - | - | - | - | $21,880 | - |
- - kWh |
- - kW-months/year |
- - $ |
$21,880 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 4.431 TRAIN OPERATORS FOR MAXIMUM OPERATING EFFICIENCY |
Savings: $312,000 Cost: $100,000 |
- | - | - | - | $312,000 | - | - | - |
- - kWh |
- - kW-months/year |
$312,000 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $475,942 Cost: $238,685 |
$24,148 | 181,061 | $21,092 | 2,225 | $308,815 | - | $121,887 | - | $24,148 181,061 kWh |
$21,092 2,225 kW-months/year |
$308,815 - $ |
$121,887 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $6,110 Cost: $5,085 |
$7,318 | 56,367 | $1,977 | 185 | $(-3,185) | - | - | - | $7,318 56,367 kWh |
$1,977 185 kW-months/year |
$(-3,185) - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes | Electricity Usage | Electricity Demand | Personnel Changes | Administrative Changes |