Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Massachusetts |
---|---|
Assessment Year | 2005 |
Principal Product | Plastic auto parts |
NAICS | 336390 - Other Motor Vehicle Parts Manufacturing |
SIC | 3714 - Motor Vehicle Parts And Accessories |
Sales | $10,000,000-$50,000,000 |
# of Employees | 181 |
Plant Area (Sq.Ft.) | 345,000 |
Annual Production | 1,165,000 Pieces |
Production Hrs. Annual | 3,624 |
Location (State) | NH |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,280,846 | 15,519,170 | kWh | $0.08 |
Electricity Demand | $349,483 | 46,645 | kW-months/year | $7.49 |
Electricity Fees | $55,829 | - | $ | - |
LPG | $896,300 | 98,726 | MMBtu | $9.08 |
TOTAL ENERGY COSTS | $2,582,458 | |||
RECOMMENDED SAVINGS* | $197,823 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $129,142 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | LPG | Electricity Usage | Electricity Demand | LPG | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $86,353 Cost: $20,000 |
- | - | $86,353 | 9,972 | - | - |
- - kWh |
$86,353 9,972 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME |
Savings: $13,684 Cost: $4,800 |
$1,043 | 12,480 | - | - | $12,641 | 1,107 |
$1,043 12,480 kWh |
- - kW-months/year |
$12,641 1,107 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $4,767 Cost: $25,000 |
$4,767 | 58,273 | - | - | - | - |
$4,767 58,273 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $318 Cost: $327 |
$401 | 4,600 | - | - | $(-83) | (-9) |
$401 4,600 kWh |
- - kW-months/year |
$(-83) (-9) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $1,718 Cost: $5,475 |
$1,307 | 15,663 | $411 | 57 | - | - |
$1,307 15,663 kWh |
$411 57 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.1116 IMPROVE COMBUSTION CONTROL CAPABILITY |
Savings: $36,304 Cost: $600 |
- | - | - | - | $36,304 | 3,179 |
- - kWh |
- - kW-months/year |
$36,304 3,179 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $54,679 Cost: $800 |
- | - | - | - | $54,679 | 4,788 |
- - kWh |
- - kW-months/year |
$54,679 4,788 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $197,823 Cost: $57,002 |
$7,518 | 91,016 | $86,764 | 10,029 | $103,541 | 9,065 | $7,518 91,016 kWh |
$86,764 10,029 kW-months/year |
$103,541 9,065 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $129,142 Cost: $51,075 |
$6,074 | 73,936 | $86,764 | 10,029 | $36,304 | 3,179 | $6,074 73,936 kWh |
$86,764 10,029 kW-months/year |
$36,304 3,179 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | LPG | Electricity Usage | Electricity Demand | LPG |