Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Massachusetts |
---|---|
Assessment Year | 2019 |
Principal Product | Water |
NAICS | 221310 - Water Supply and Irrigation Systems |
SIC | 4941 - Water Supply |
Sales | $1,000,000-$5,000,000 |
# of Employees | 5 |
Plant Area (Sq.Ft.) | 40,000 |
Annual Production | 365,000 Thousand Gallons |
Production Hrs. Annual | 8,760 |
Location (State) | CT |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $65,736 | 701,342 | kWh | $0.09 |
Electricity Demand | $26,605 | 1,442 | kW-months/year | $18.45 |
Electricity Fees | $4,766 | - | $ | - |
LPG | $7,930 | 365 | MMBtu | $21.73 |
TOTAL ENERGY COSTS | $105,037 | |||
RECOMMENDED SAVINGS* | $18,470 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $5,232 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | LPG | Electricity Usage | Electricity Demand | LPG | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $4,315 Cost: $14,350 |
$14,928 | 158,805 | $4,096 | 222 | $(-14,709) | (-677) |
$14,928 158,805 kWh |
$4,096 222 kW-months/year |
$(-14,709) (-677) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $7,245 Cost: $6,660 |
$3,758 | 39,980 | $3,487 | 189 | - | - |
$3,758 39,980 kWh |
$3,487 189 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $3,193 Cost: $200 |
$1,846 | 19,636 | - | - | $1,347 | 62 |
$1,846 19,636 kWh |
- - kW-months/year |
$1,347 62 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 3.1191 CHANGE PROCEDURES / EQUIPMENT / OPERATING CONDITIONS |
Savings: $1,678 Cost: $300 |
$1,678 | 17,852 | - | - | - | - |
$1,678 17,852 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,405 Cost: $2,499 |
$704 | 7,486 | $701 | 38 | - | - |
$704 7,486 kWh |
$701 38 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $634 Cost: $200 |
$634 | 6,741 | - | - | - | - |
$634 6,741 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $18,470 Cost: $24,209 |
$23,548 | 250,500 | $8,284 | 449 | $(-13,362) | (-615) | $23,548 250,500 kWh |
$8,284 449 kW-months/year |
$(-13,362) (-615) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $5,232 Cost: $2,899 |
$3,184 | 33,863 | $701 | 38 | $1,347 | 62 | $3,184 33,863 kWh |
$701 38 kW-months/year |
$1,347 62 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | LPG | Electricity Usage | Electricity Demand | LPG |