Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
IAC Center | University of Maine |
---|---|
Assessment Year | 1997 |
Principal Product | Glued Wood Dimensions |
NAICS | n/a |
SIC | 2426 - Hardwood Dimension & Flooring Mills |
Sales | $5,000,000-$10,000,000 |
# of Employees | 110 |
Plant Area (Sq.Ft.) | 50,000 |
Annual Production | 9,000,000 Thousand Feet |
Production Hrs. Annual | 4,100 |
Location (State) | ME |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $175,918 | 2,940,797 | kWh | $0.06 |
Electricity Demand | $70,387 | 10,726 | kW-months/year | $6.56 |
Electricity Fees | $6,453 | - | $ | - |
LPG | $2,678 | 179 | MMBtu | $14.96 |
Fuel Oil #1 | $1,509 | 175 | MMBtu | $8.62 |
Fuel Oil #2 | $34,620 | 4,162 | MMBtu | $8.32 |
Other Energy | $5,811 | 585 | MMBtu | $9.93 |
TOTAL ENERGY COSTS | $297,376 | |||
RECOMMENDED SAVINGS* | $22,747 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $15,547 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Fuel Oil #2 | Wood | Solid Waste (non-haz) | Administrative Changes | Electricity Usage | Electricity Demand | Fuel Oil #2 | Wood | Solid Waste (non-haz) | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | MMBtu | $ | lb | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 4.231 PURCHASE EQUIPMENT INSTEAD OF LEASING |
Savings: $7,200 Cost: $27,375 |
- | - | - | - | - | - | - | - | - | - | $7,200 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
$7,200 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $5,389 Cost: $8,204 |
$4,995 | 53,634 | $394 | 60 | - | - | - | - | - | - | - | - |
$4,995 53,634 kWh |
$394 60 kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $3,895 Cost: $13,215 |
$3,214 | 53,341 | $681 | 103 | - | - | - | - | - | - | - | - |
$3,214 53,341 kWh |
$681 103 kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $2,941 Cost: $3,276 |
$2,941 | 48,945 | - | - | - | - | - | - | - | - | - | - |
$2,941 48,945 kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $1,517 Cost: $3,844 |
$1,492 | 24,912 | $683 | 104 | $(-658) | (-106) | - | - | - | - | - | - |
$1,492 24,912 kWh |
$683 104 kW-months/year |
$(-658) (-106) MMBtu |
- - MMBtu |
- - lb |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $597 Cost: $603 |
- | - | - | - | - | - | $597 | 354 | - | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$597 354 MMBtu |
- - lb |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $564 Cost: $325 |
$564 | 9,379 | - | - | - | - | - | - | - | - | - | - |
$564 9,379 kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.8121 APPLY FOR TAX-FREE STATUS FOR ENERGY PURCHASES |
Savings: $144 Cost: - |
- | - | - | - | - | - | - | - | - | - | $144 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
- - lb |
$144 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 3.5248 SEPARATE AND RECYCLE SCRAP METAL TO FOUNDRY OR FOR SALE |
Savings: $500 Cost: - |
- | - | - | - | - | - | - | - | $500 | 40,000 | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
$500 40,000 lb |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $22,747 Cost: $56,842 |
$13,206 | 190,211 | $1,758 | 267 | $(-658) | (-106) | $597 | 354 | $500 | 40,000 | $7,344 | - | $13,206 190,211 kWh |
$1,758 267 kW-months/year |
$(-658) (-106) MMBtu |
$597 354 MMBtu |
$500 40,000 lb |
$7,344 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $15,547 Cost: $29,467 |
$13,206 | 190,211 | $1,758 | 267 | $(-658) | (-106) | $597 | 354 | $500 | 40,000 | $144 | - | $13,206 190,211 kWh |
$1,758 267 kW-months/year |
$(-658) (-106) MMBtu |
$597 354 MMBtu |
$500 40,000 lb |
$144 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | MMBtu | $ | lb | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Fuel Oil #2 | Wood | Solid Waste (non-haz) | Administrative Changes | Electricity Usage | Electricity Demand | Fuel Oil #2 | Wood | Solid Waste (non-haz) | Administrative Changes |