Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2008 |
Principal Product | Circuit Boards |
NAICS | 334418 - Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3672 - Printed Circuit Boards |
Sales | $10,000,000-$50,000,000 |
# of Employees | 300 |
Plant Area (Sq.Ft.) | 170,000 |
Annual Production | 39,500 Pieces |
Production Hrs. Annual | 7,200 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $924,085 | 12,164,480 | kWh | $0.08 |
Electricity Demand | $82,204 | 25,584 | kW-months/year | $3.21 |
Electricity Fees | $148,104 | - | $ | - |
TOTAL ENERGY COSTS | $1,154,393 | |||
RECOMMENDED SAVINGS* | $428,536 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $169,953 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $256,906 Cost: $645,000 |
$243,633 | 2,784,219 | $13,273 | 3,814 |
$243,633 2,784,219 kWh |
$13,273 3,814 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $60,893 Cost: $2,040 |
$54,667 | 821,322 | $6,226 | 1,789 |
$54,667 821,322 kWh |
$6,226 1,789 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $32,290 Cost: $43,681 |
$29,715 | 339,595 | $2,575 | 740 |
$29,715 339,595 kWh |
$2,575 740 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $19,060 Cost: $1,210 |
$18,727 | 214,025 | $333 | 96 |
$18,727 214,025 kWh |
$333 96 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,713 Cost: $40 |
$1,568 | 17,971 | $145 | 48 |
$1,568 17,971 kWh |
$145 48 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4323 USE OPTIMUM SIZE AND CAPACITY EQUIPMENT |
Savings: $1,677 Cost: $3,475 |
$1,537 | 17,571 | $140 | 41 |
$1,537 17,571 kWh |
$140 41 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $33,795 Cost: $22,516 |
$32,049 | 366,274 | $1,746 | 42 |
$32,049 366,274 kWh |
$1,746 42 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $22,202 Cost: $3,320 |
$21,008 | 240,092 | $1,194 | 343 |
$21,008 240,092 kWh |
$1,194 343 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $428,536 Cost: $721,282 |
$402,904 | 4,801,069 | $25,632 | 6,913 | $402,904 4,801,069 kWh |
$25,632 6,913 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $169,953 Cost: $72,807 |
$157,734 | 1,999,279 | $12,219 | 3,058 | $157,734 1,999,279 kWh |
$12,219 3,058 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand |