Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2013 |
Principal Product | Electronic Circuits |
NAICS | 334419 - Other Electronic Component Manufacturing |
SIC | 3679 - Electronic Components, Nec |
Sales | $50,000,000-$100,000,000 |
# of Employees | 231 |
Plant Area (Sq.Ft.) | 100,000 |
Annual Production | 300,000 Pieces |
Production Hrs. Annual | 2,340 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $284,264 | 4,337,539 | kWh | $0.07 |
Electricity Demand | $119,485 | 11,578 | kW-months/year | $10.32 |
Electricity Fees | $11,602 | - | $ | - |
TOTAL ENERGY COSTS | $415,351 | |||
RECOMMENDED SAVINGS* | $126,490 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $93,920 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $30,611 Cost: $1,800 |
$20,590 | 328,130 | $10,021 | 971 |
$20,590 328,130 kWh |
$10,021 971 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $26,976 Cost: $407 |
$15,065 | 240,084 | $11,911 | 1,154 |
$15,065 240,084 kWh |
$11,911 1,154 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $24,698 Cost: $160 |
$18,536 | 279,448 | $6,162 | 597 |
$18,536 279,448 kWh |
$6,162 597 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7496 INSTALL PARTITIONS TO REDUCE SIZE OF CONDITIONED SPACE |
Savings: $13,325 Cost: $13,200 |
$7,226 | 115,149 | $6,099 | 591 |
$7,226 115,149 kWh |
$6,099 591 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD |
Savings: $12,407 Cost: $1,680 |
$6,731 | 107,262 | $5,676 | 550 |
$6,731 107,262 kWh |
$5,676 550 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,737 Cost: $1,660 |
$2,624 | 41,824 | $1,113 | 108 |
$2,624 41,824 kWh |
$1,113 108 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $3,337 Cost: $80 |
$2,036 | 32,452 | $1,301 | 126 |
$2,036 32,452 kWh |
$1,301 126 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $2,960 Cost: $7,502 |
$1,659 | 24,579 | $1,301 | 126 |
$1,659 24,579 kWh |
$1,301 126 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $2,930 Cost: $896 |
$1,590 | 25,326 | $1,340 | 130 |
$1,590 25,326 kWh |
$1,340 130 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $1,980 Cost: $440 |
$1,072 | 17,082 | $908 | 88 |
$1,072 17,082 kWh |
$908 88 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,631 Cost: $3,190 |
$1,092 | 17,400 | $539 | 52 |
$1,092 17,400 kWh |
$539 52 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $1,214 Cost: $1,694 |
$657 | 10,474 | $557 | 54 |
$657 10,474 kWh |
$557 54 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $684 Cost: $2,000 |
$396 | 6,318 | $288 | 22 |
$396 6,318 kWh |
$288 22 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $126,490 Cost: $34,709 |
$79,274 | 1,245,528 | $47,216 | 4,569 | $79,274 1,245,528 kWh |
$47,216 4,569 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $93,920 Cost: $30,966 |
$61,151 | 956,718 | $32,769 | 3,175 | $61,151 956,718 kWh |
$32,769 3,175 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand |