Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2015 |
Principal Product | Newspapers |
NAICS | 323111 - Commercial Printing (except Screen and Books) |
SIC | 2711 - Newspapers |
Sales | $50,000,000-$100,000,000 |
# of Employees | 470 |
Plant Area (Sq.Ft.) | 130,000 |
Annual Production | 25,000,000 Pieces |
Production Hrs. Annual | 8,736 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $524,366 | 14,238,000 | kWh | $0.04 |
Electricity Demand | $482,465 | 38,461 | kW-months/year | $12.54 |
TOTAL ENERGY COSTS | $1,006,831 | |||
RECOMMENDED SAVINGS* | $100,919 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $49,563 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Water Consumption | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Water Consumption | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | Tgal | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD |
Savings: $36,507 Cost: $57,817 |
$18,895 | 510,668 | $17,612 | 1,404 | - | - | - | - |
$18,895 510,668 kWh |
$17,612 1,404 kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $8,849 Cost: $480 |
$6,039 | 163,217 | $2,810 | 224 | - | - | - | - |
$6,039 163,217 kWh |
$2,810 224 kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 3.4151 MINIMIZE WATER USAGE |
Savings: $8,287 Cost: $16,600 |
- | - | - | - | $8,287 | - | - | - |
- - kWh |
- - kW-months/year |
$8,287 - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $6,969 Cost: $1,660 |
$4,548 | 122,914 | $2,421 | 193 | - | - | - | - |
$4,548 122,914 kWh |
$2,421 193 kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $6,933 Cost: $912 |
$6,933 | 187,387 | - | - | - | - | - | - |
$6,933 187,387 kWh |
- - kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7141 LOWER LIGHT FIXTURES IN HIGH CEILING AREAS |
Savings: $6,562 Cost: $16,470 |
$4,480 | 121,081 | $2,082 | 166 | - | - | - | - |
$4,480 121,081 kWh |
$2,082 166 kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $6,447 Cost: $3,660 |
$4,402 | 118,985 | $2,045 | 163 | - | - | - | - |
$4,402 118,985 kWh |
$2,045 163 kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $6,157 Cost: $11,750 |
$4,200 | 113,519 | $1,957 | 156 | - | - | - | - |
$4,200 113,519 kWh |
$1,957 156 kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS |
Savings: $5,843 Cost: $6,280 |
- | - | $3,751 | 299 | - | - | $2,092 | - |
- - kWh |
$3,751 299 kW-months/year |
- - Tgal |
$2,092 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $4,759 Cost: $80 |
$2,589 | 69,965 | $2,170 | 173 | - | - | - | - |
$2,589 69,965 kWh |
$2,170 173 kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $3,476 Cost: $1,080 |
$3,476 | 93,694 | - | - | - | - | - | - |
$3,476 93,694 kWh |
- - kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $130 Cost: $375 |
$89 | 2,400 | $41 | 3 | - | - | - | - |
$89 2,400 kWh |
$41 3 kW-months/year |
- - Tgal |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $100,919 Cost: $117,164 |
$55,651 | 1,503,830 | $34,889 | 2,781 | $8,287 | - | $2,092 | - | $55,651 1,503,830 kWh |
$34,889 2,781 kW-months/year |
$8,287 - Tgal |
$2,092 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $49,563 Cost: $26,277 |
$32,276 | 872,081 | $15,195 | 1,211 | - | - | $2,092 | - | $32,276 872,081 kWh |
$15,195 1,211 kW-months/year |
- - Tgal |
$2,092 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | Tgal | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Water Consumption | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Water Consumption | One-time Revenue or Avoided Cost |