Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2015 |
Principal Product | Newspapers |
NAICS | 323111 - Commercial Printing (except Screen and Books) |
SIC | 2711 - Newspapers |
Sales | $100,000,000-$500,000,000 |
# of Employees | 500 |
Plant Area (Sq.Ft.) | 328,000 |
Annual Production | 14,000 Tons |
Production Hrs. Annual | 8,736 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $778,305 | 9,787,560 | kWh | $0.08 |
Electricity Demand | $258,197 | 32,767 | kW-months/year | $7.88 |
Electricity Fees | $104,646 | - | $ | - |
TOTAL ENERGY COSTS | $1,141,147 | |||
RECOMMENDED SAVINGS* | $105,488 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $69,945 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Electricity Usage | Electricity Demand | Electricity Fees | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $25,305 Cost: $11,600 |
$22,255 | 281,709 | $3,050 | 387 | - | - |
$22,255 281,709 kWh |
$3,050 387 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $24,948 Cost: $1,660 |
$21,383 | 270,673 | $3,565 | 452 | - | - |
$21,383 270,673 kWh |
$3,565 452 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $11,055 Cost: $676 |
$11,055 | 139,942 | - | - | - | - |
$11,055 139,942 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $9,296 Cost: $40 |
$8,177 | 103,500 | $1,119 | 142 | - | - |
$8,177 103,500 kWh |
$1,119 142 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $6,998 Cost: $2,680 |
$6,076 | 76,906 | $922 | 117 | - | - |
$6,076 76,906 kWh |
$922 117 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS |
Savings: $6,524 Cost: $6,280 |
- | - | $3,317 | 421 | $3,207 | - |
- - kWh |
$3,317 421 kW-months/year |
$3,207 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7229 AIR CONDITION ONLY SPACE NECESSARY |
Savings: $5,757 Cost: $1,500 |
$5,064 | 64,106 | $693 | 88 | - | - |
$5,064 64,106 kWh |
$693 88 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $4,632 Cost: $570 |
$4,632 | 58,630 | - | - | - | - |
$4,632 58,630 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $4,481 Cost: $12,150 |
$3,941 | 49,883 | $540 | 69 | - | - |
$3,941 49,883 kWh |
$540 69 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $3,212 Cost: $40 |
$2,825 | 35,764 | $387 | 49 | - | - |
$2,825 35,764 kWh |
$387 49 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $1,371 Cost: $3,309 |
$1,206 | 15,266 | $165 | 21 | - | - |
$1,206 15,266 kWh |
$165 21 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,078 Cost: $1,638 |
$1,078 | 13,571 | - | - | - | - |
$1,078 13,571 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $831 Cost: $20 |
$729 | 9,225 | $102 | 13 | - | - |
$729 9,225 kWh |
$102 13 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $105,488 Cost: $42,163 |
$88,421 | 1,119,175 | $13,860 | 1,759 | $3,207 | - | $88,421 1,119,175 kWh |
$13,860 1,759 kW-months/year |
$3,207 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $69,945 Cost: $16,913 |
$57,161 | 723,477 | $9,577 | 1,215 | $3,207 | - | $57,161 723,477 kWh |
$9,577 1,215 kW-months/year |
$3,207 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Electricity Usage | Electricity Demand | Electricity Fees |