Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2017 |
Principal Product | treated water |
NAICS | 221320 - Sewage Treatment Facilities |
SIC | 4952 - Sewerage Systems |
Sales | $10,000,000-$50,000,000 |
# of Employees | 130 |
Plant Area (Sq.Ft.) | 13,000,000 |
Annual Production | 100,000 Thousand Gallons |
Production Hrs. Annual | 8,760 |
Location (State) | FL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $5,716,458 | 141,744,000 | kWh | $0.04 |
Electricity Demand | $2,908,255 | 533,253 | kW-months/year | $5.45 |
Electricity Fees | $628,471 | - | $ | - |
TOTAL ENERGY COSTS | $9,253,184 | |||
RECOMMENDED SAVINGS* | $2,239,259 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $2,174,576 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Other Gas | Administrative Changes | Electricity Usage | Electricity Demand | Other Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1336 INSTALL EQUIPMENT TO UTILIZE WASTE FUEL |
Savings: $1,663,200 Cost: $4,120,000 |
$1,401,600 | 35,040,000 | $261,600 | 48,000 | $(0) | (-120,450) | - | - |
$1,401,600 35,040,000 kWh |
$261,600 48,000 kW-months/year |
$(0) (-120,450) MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2696 USE EXCESS COLD PROCESS FLUID FOR INDUSTRIAL COOLING NEEDS |
Savings: $314,391 Cost: $1,004,370 |
$264,941 | 6,623,524 | $49,450 | 9,073 | - | - | - | - |
$264,941 6,623,524 kWh |
$49,450 9,073 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $171,697 Cost: $338,000 |
$127,826 | 3,195,648 | $23,871 | 4,380 | - | - | $20,000 | - |
$127,826 3,195,648 kWh |
$23,871 4,380 kW-months/year |
- - MMBtu |
$20,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $32,930 Cost: $6,000 |
$27,752 | 693,792 | $5,178 | 950 | - | - | - | - |
$27,752 693,792 kWh |
$5,178 950 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE |
Savings: $31,753 Cost: $112,000 |
$9,102 | 227,550 | $22,651 | 4,156 | - | - | - | - |
$9,102 227,550 kWh |
$22,651 4,156 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $25,288 Cost: $72,396 |
$18,414 | 460,338 | $6,874 | 1,261 | - | - | - | - |
$18,414 460,338 kWh |
$6,874 1,261 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $2,239,259 Cost: $5,652,766 |
$1,849,635 | 46,240,852 | $369,624 | 67,820 | $(0) | (-120,450) | $20,000 | - | $1,849,635 46,240,852 kWh |
$369,624 67,820 kW-months/year |
$(0) (-120,450) MMBtu |
$20,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $2,174,576 Cost: $5,534,766 |
$1,812,781 | 45,319,510 | $341,795 | 62,714 | $(0) | (-120,450) | $20,000 | - | $1,812,781 45,319,510 kWh |
$341,795 62,714 kW-months/year |
$(0) (-120,450) MMBtu |
$20,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Other Gas | Administrative Changes | Electricity Usage | Electricity Demand | Other Gas | Administrative Changes |