Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Missouri, Rolla |
---|---|
Assessment Year | 1999 |
Principal Product | Automotive Engines |
NAICS | n/a |
SIC | 3599 - Industrial Machinery, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 148 |
Plant Area (Sq.Ft.) | 42,200 |
Annual Production | 13,000 Pieces |
Production Hrs. Annual | 4,160 |
Location (State) | MO |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $48,768 | 1,204,572 | kWh | $0.04 |
Electricity Demand | $23,133 | 402 | kW-months/year | $57.54 |
Electricity Fees | $3,397 | - | $ | - |
Natural Gas | $34,496 | 7,559 | MMBtu | $4.56 |
TOTAL ENERGY COSTS | $117,327 | |||
RECOMMENDED SAVINGS* | $29,110 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $6,582 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Other Liquid (non-haz) | Solid Waste (non-haz) | Administrative Changes | Electricity Usage | Electricity Demand | Other Liquid (non-haz) | Solid Waste (non-haz) | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | gal | $ | lb | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,430 Cost: $3,948 |
$1,085 | 25,205 | $345 | 6 | - | - | - | - | - | - |
$1,085 25,205 kWh |
$345 6 kW-months/year |
- - gal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $2,291 Cost: $97 |
$1,733 | 40,152 | $558 | 10 | - | - | - | - | - | - |
$1,733 40,152 kWh |
$558 10 kW-months/year |
- - gal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,662 Cost: $80 |
$1,259 | 29,015 | $403 | 7 | - | - | - | - | - | - |
$1,259 29,015 kWh |
$403 7 kW-months/year |
- - gal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $1,816 Cost: $2,451 |
$1,373 | 31,653 | $443 | 8 | - | - | - | - | - | - |
$1,373 31,653 kWh |
$443 8 kW-months/year |
- - gal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 3.5316 CONTRACT A WOOD PALLET RECYCLING COMPANY |
Savings: $2,475 Cost: - |
- | - | - | - | - | - | $2,475 | 825 | - | - |
- - kWh |
- - kW-months/year |
- - gal |
$2,475 825 lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 3.6124 BURN WASTE OIL FOR HEAT |
Savings: $4,200 Cost: $2,000 |
- | - | - | - | $4,200 | 6,000 | - | - | - | - |
- - kWh |
- - kW-months/year |
$4,200 6,000 gal |
- - lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 4.652 REPLACE EXISTING EQUIPMENT WITH MORE SUITABLE SUBSTITUTES |
Savings: $15,236 Cost: $2,500 |
- | - | - | - | - | - | - | - | $15,236 | - |
- - kWh |
- - kW-months/year |
- - gal |
- - lb |
$15,236 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $29,110 Cost: $11,076 |
$5,450 | 126,025 | $1,749 | 31 | $4,200 | 6,000 | $2,475 | 825 | $15,236 | - | $5,450 126,025 kWh |
$1,749 31 kW-months/year |
$4,200 6,000 gal |
$2,475 825 lb |
$15,236 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $6,582 Cost: $2,548 |
$3,106 | 71,805 | $1,001 | 18 | - | - | $2,475 | 825 | - | - | $3,106 71,805 kWh |
$1,001 18 kW-months/year |
- - gal |
$2,475 825 lb |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | gal | $ | lb | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Other Liquid (non-haz) | Solid Waste (non-haz) | Administrative Changes | Electricity Usage | Electricity Demand | Other Liquid (non-haz) | Solid Waste (non-haz) | Administrative Changes |