Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Mississippi State |
---|---|
Assessment Year | 2003 |
Principal Product | Wooden furniture parts |
NAICS | 337215 - Showcase, Partition, Shelving, and Locker Manufacturing |
SIC | 2426 - Hardwood Dimension & Flooring Mills |
Sales | $10,000,000-$50,000,000 |
# of Employees | 250 |
Plant Area (Sq.Ft.) | 275,000 |
Annual Production | 242,601 Pieces |
Production Hrs. Annual | 2,000 |
Location (State) | MS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $138,397 | 4,070,000 | kWh | $0.03 |
Electricity Demand | $156,206 | 16,513 | kW-months/year | $9.46 |
Electricity Fees | $(-8,890) | - | $ | - |
Natural Gas | $129,671 | 25,071 | MMBtu | $5.17 |
TOTAL ENERGY COSTS | $457,055 | |||
RECOMMENDED SAVINGS* | $57,535 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $17,007 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3134 SHIFT FROM DAYTIME TO NIGHTTIME OPERATION |
Savings: $33,740 Cost: - |
- | - | $33,241 | 3,133 | $499 | - | - | - |
- - kWh |
$33,241 3,133 kW-months/year |
$499 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $11,538 Cost: $8,188 |
$3,888 | 117,454 | $7,480 | 705 | $170 | - | - | - |
$3,888 117,454 kWh |
$7,480 705 kW-months/year |
$170 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,532 Cost: $411 |
$3,480 | 105,156 | - | - | $52 | - | - | - |
$3,480 105,156 kWh |
- - kW-months/year |
$52 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $2,878 Cost: $4,320 |
$968 | 29,251 | $1,867 | 176 | $43 | - | - | - |
$968 29,251 kWh |
$1,867 176 kW-months/year |
$43 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $2,829 Cost: $3,710 |
$2,787 | 84,207 | - | - | $42 | - | - | - |
$2,787 84,207 kWh |
- - kW-months/year |
$42 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $1,537 Cost: $1,000 |
- | - | - | - | - | - | $1,537 | 297 |
- - kWh |
- - kW-months/year |
- - $ |
$1,537 297 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $1,081 Cost: $355 |
$333 | 10,071 | $732 | 69 | $16 | - | - | - |
$333 10,071 kWh |
$732 69 kW-months/year |
$16 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $400 Cost: $355 |
$394 | 11,903 | - | - | $6 | - | - | - |
$394 11,903 kWh |
- - kW-months/year |
$6 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $57,535 Cost: $18,339 |
$11,850 | 358,042 | $43,320 | 4,083 | $828 | - | $1,537 | 297 | $11,850 358,042 kWh |
$43,320 4,083 kW-months/year |
$828 - $ |
$1,537 297 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $17,007 Cost: $9,954 |
$7,762 | 234,513 | $7,480 | 705 | $228 | - | $1,537 | 297 | $7,762 234,513 kWh |
$7,480 705 kW-months/year |
$228 - $ |
$1,537 297 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas |