Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Michigan State University |
---|---|
Assessment Year | 2023 |
Principal Product | Automotive Equipment for Off Road Vehicle Applications |
NAICS | 334419 - Other Electronic Component Manufacturing |
SIC | 3679 - Electronic Components, Nec |
Sales | $50,000,000-$100,000,000 |
# of Employees | 220 |
Plant Area (Sq.Ft.) | 175,000 |
Annual Production | 2,000,000 Pieces |
Production Hrs. Annual | 6,300 |
Location (State) | MI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $269,132 | 3,563,486 | kWh | $0.08 |
Electricity Demand | $176,440 | 9,232 | kW-months/year | $19.11 |
Electricity Fees | $20,779 | - | $ | - |
Natural Gas | $27,093 | 2,301 | MMBtu | $11.78 |
TOTAL ENERGY COSTS | $493,445 | |||
RECOMMENDED SAVINGS* | $44,789 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $15,281 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $1,852 Cost: - |
$1,378 | 18,129 | $475 | 25 | - | - | - | - |
$1,378 18,129 kWh |
$475 25 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $388 Cost: - |
$289 | 3,797 | $99 | 5 | - | - | - | - |
$289 3,797 kWh |
$99 5 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $10,129 Cost: $49,885 |
$840 | 11,052 | $289 | 15 | - | - | $9,000 | - |
$840 11,052 kWh |
$289 15 kW-months/year |
- - MMBtu |
$9,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $1,737 Cost: - |
$1,291 | 16,993 | $445 | 23 | - | - | - | - |
$1,291 16,993 kWh |
$445 23 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $756 Cost: - |
$756 | 9,951 | - | - | - | - | - | - |
$756 9,951 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,296 Cost: $30 |
$1,296 | 17,051 | - | - | - | - | - | - |
$1,296 17,051 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,370 Cost: - |
$1,370 | 18,023 | - | - | - | - | - | - |
$1,370 18,023 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $305 Cost: $1,240 |
$227 | 2,987 | $78 | 4 | - | - | - | - |
$227 2,987 kWh |
$78 4 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7212 INSTALL OR UPGRADE INSULATION ON HVAC DISTRIBUTION SYSTEMS |
Savings: $3,433 Cost: $3,037 |
$961 | 12,650 | $806 | 42 | $1,665 | 141 | - | - |
$961 12,650 kWh |
$806 42 kW-months/year |
$1,665 141 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $902 Cost: - |
$356 | 4,680 | $122 | 6 | $424 | 36 | - | - |
$356 4,680 kWh |
$122 6 kW-months/year |
$424 36 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7231 USE RADIANT HEATER FOR SPOT HEATING |
Savings: $4,730 Cost: $5,760 |
- | - | - | - | $4,730 | 402 | - | - |
- - kWh |
- - kW-months/year |
$4,730 402 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $12,544 Cost: $17,271 |
$1,550 | 20,398 | - | - | $10,994 | 934 | - | - |
$1,550 20,398 kWh |
- - kW-months/year |
$10,994 934 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $5,347 Cost: $25,171 |
$5,347 | 53,468 | - | - | - | - | - | - |
$5,347 53,468 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $44,789 Cost: $102,394 |
$15,661 | 189,179 | $2,315 | 121 | $17,813 | 1,513 | $9,000 | - | $15,661 189,179 kWh |
$2,315 121 kW-months/year |
$17,813 1,513 MMBtu |
$9,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $15,281 Cost: $49,885 |
$4,902 | 64,495 | $955 | 50 | $424 | 36 | $9,000 | - | $4,902 64,495 kWh |
$955 50 kW-months/year |
$424 36 MMBtu |
$9,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |