Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | North Carolina State |
---|---|
Assessment Year | 1998 |
Principal Product | Electric light assemblies |
NAICS | n/a |
SIC | 3646 - Commercial Lighting Fixtures |
Sales | $10,000,000-$50,000,000 |
# of Employees | 210 |
Plant Area (Sq.Ft.) | 435,000 |
Annual Production | 10,000,000 Pieces |
Production Hrs. Annual | 4,000 |
Location (State) | VA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $108,123 | 4,582,943 | kWh | $0.02 |
Electricity Demand | $68,486 | 8,352 | kW-months/year | $8.20 |
Electricity Fees | $120 | - | $ | - |
Natural Gas | $43,214 | 6,505 | MMBtu | $6.64 |
TOTAL ENERGY COSTS | $219,943 | |||
RECOMMENDED SAVINGS* | $62,598 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | By-product Production | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | By-product Production | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $541 Cost: $800 |
- | - | - | - | $541 | 81 | - | - | - | - |
- - kWh |
- - kW-months/year |
$541 81 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $16,691 Cost: $18,850 |
$16,691 | 634,818 | - | - | - | - | - | - | - | - |
$16,691 634,818 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7131 ADD AREA LIGHTING SWITCHES |
Savings: $91 Cost: $300 |
$91 | 3,810 | - | - | - | - | - | - | - | - |
$91 3,810 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $3,508 Cost: $500 |
$1,146 | 48,652 | $2,362 | 288 | - | - | - | - | - | - |
$1,146 48,652 kWh |
$2,362 288 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7145 INSTALL SKYLIGHTS |
Savings: $10,344 Cost: $36,000 |
$4,342 | 184,056 | $6,002 | 732 | - | - | - | - | - | - |
$4,342 184,056 kWh |
$6,002 732 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2711 UTILIZE OUTSIDE AIR INSTEAD OF CONDITIONED AIR FOR DRYING |
Savings: $3,423 Cost: $3,000 |
$879 | 33,411 | $1,984 | 242 | - | - | $560 | - | - | - |
$879 33,411 kWh |
$1,984 242 kW-months/year |
- - MMBtu |
$560 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 4.521 CLEAR AND RENT EXISTING SPACE |
Savings: $28,000 Cost: $20,500 |
- | - | - | - | - | - | - | - | $28,000 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
$28,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $62,598 Cost: $79,950 |
$23,149 | 904,747 | $10,348 | 1,262 | $541 | 81 | $560 | - | $28,000 | - | $23,149 904,747 kWh |
$10,348 1,262 kW-months/year |
$541 81 MMBtu |
$560 - $ |
$28,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | By-product Production | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | By-product Production |