Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | North Carolina State |
---|---|
Assessment Year | 2002 |
Principal Product | Ladies hosiery |
NAICS | n/a |
SIC | 2252 - Hosiery, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 439 |
Plant Area (Sq.Ft.) | 160,000 |
Annual Production | 29,448,000 Pieces |
Production Hrs. Annual | 8,400 |
Location (State) | NC |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $476,809 | 13,862,400 | kWh | $0.03 |
Electricity Demand | $378,515 | 33,646 | kW-months/year | $11.25 |
Electricity Fees | $31,983 | - | $ | - |
Natural Gas | $374,891 | 80,974 | MMBtu | $4.63 |
TOTAL ENERGY COSTS | $1,262,198 | |||
RECOMMENDED SAVINGS* | $63,539 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $19,167 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1133 ADJUST BURNERS FOR EFFICIENT OPERATION |
Savings: $10,271 Cost: $1,000 |
- | - | - | - | $10,271 | 2,218 | - | - |
- - kWh |
- - kW-months/year |
$10,271 2,218 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2127 FLASH CONDENSATE TO PRODUCE LOWER PRESSURE STEAM |
Savings: $9,455 Cost: $10,000 |
- | - | - | - | $8,781 | 1,897 | $674 | 173,381 |
- - kWh |
- - kW-months/year |
$8,781 1,897 MMBtu |
$674 173,381 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 3.4113 TREAT AND REUSE RINSE WATERS |
Savings: $28,786 Cost: $5,000 |
- | - | - | - | $21,802 | 4,955 | $6,984 | 1,800,000 |
- - kWh |
- - kW-months/year |
$21,802 4,955 MMBtu |
$6,984 1,800,000 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $6,131 Cost: $10,062 |
- | - | - | - | $6,131 | 1,324 | - | - |
- - kWh |
- - kW-months/year |
$6,131 1,324 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $547 Cost: $369 |
$339 | 9,690 | $208 | 18 | - | - | - | - |
$339 9,690 kWh |
$208 18 kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7228 AVOID INTRODUCING HOT, HUMID, OR DIRTY AIR INTO HVAC SYSTEM |
Savings: $2,368 Cost: $1,200 |
$1,335 | 38,175 | $1,033 | 92 | - | - | - | - |
$1,335 38,175 kWh |
$1,033 92 kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7228 AVOID INTRODUCING HOT, HUMID, OR DIRTY AIR INTO HVAC SYSTEM |
Savings: $5,981 Cost: $3,100 |
$1,356 | 38,780 | $4,625 | 412 | - | - | - | - |
$1,356 38,780 kWh |
$4,625 412 kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $63,539 Cost: $30,731 |
$3,030 | 86,645 | $5,866 | 522 | $46,985 | 10,394 | $7,658 | 1,973,381 | $3,030 86,645 kWh |
$5,866 522 kW-months/year |
$46,985 10,394 MMBtu |
$7,658 1,973,381 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $19,167 Cost: $5,669 |
$3,030 | 86,645 | $5,866 | 522 | $10,271 | 2,218 | - | - | $3,030 86,645 kWh |
$5,866 522 kW-months/year |
$10,271 2,218 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Water Disposal | Electricity Usage | Electricity Demand | Natural Gas | Water Disposal |