Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | North Carolina State |
---|---|
Assessment Year | 2010 |
Principal Product | Perlite |
NAICS | 327992 - Ground or Treated Mineral and Earth Manufacturing |
SIC | 3295 - Minerals, Ground Or Treated |
Sales | $5,000,000-$10,000,000 |
# of Employees | 10 |
Plant Area (Sq.Ft.) | 8,275 |
Annual Production | 24,000,000 Pounds |
Production Hrs. Annual | 4,800 |
Location (State) | NC |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $57,778 | 820,000 | kWh | $0.07 |
Electricity Demand | $12,034 | 2,461 | kW-months/year | $4.89 |
Electricity Fees | $2,459 | - | $ | - |
Natural Gas | $168,946 | 33,826 | MMBtu | $4.99 |
TOTAL ENERGY COSTS | $241,217 | |||
RECOMMENDED SAVINGS* | $17,976 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $5,008 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $11,924 Cost: $26,000 |
- | - | - | - | $11,924 | 2,347 | - | - | - | - |
- - kWh |
- - kW-months/year |
$11,924 2,347 MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $1,188 Cost: $1,991 |
$1,012 | 14,398 | $176 | 36 | - | - | - | - | - | - |
$1,012 14,398 kWh |
$176 36 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $1,044 Cost: $680 |
$1,044 | 14,850 | - | - | - | - | - | - | - | - |
$1,044 14,850 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,335 Cost: $50 |
$1,137 | 16,176 | $198 | 40 | - | - | - | - | - | - |
$1,137 16,176 kWh |
$198 40 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $305 Cost: $100 |
$566 | 8,057 | $99 | 20 | - | - | $(-300) | - | $(-60) | - |
$566 8,057 kWh |
$99 20 kW-months/year |
- - MMBtu |
$(-300) - $ |
$(-60) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $556 Cost: $1,692 |
$525 | 7,462 | $91 | 18 | - | - | $(-82) | - | $22 | - |
$525 7,462 kWh |
$91 18 kW-months/year |
- - MMBtu |
$(-82) - $ |
$22 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $488 Cost: $562 |
$326 | 4,631 | $81 | 17 | - | - | - | - | $81 | - |
$326 4,631 kWh |
$81 17 kW-months/year |
- - MMBtu |
- - $ |
$81 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $868 Cost: $1,450 |
$790 | 11,232 | $78 | 16 | - | - | - | - | - | - |
$790 11,232 kWh |
$78 16 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $268 Cost: $499 |
$268 | 3,807 | - | - | - | - | - | - | - | - |
$268 3,807 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $17,976 Cost: $33,024 |
$5,668 | 80,613 | $723 | 147 | $11,924 | 2,347 | $(-382) | - | $43 | - | $5,668 80,613 kWh |
$723 147 kW-months/year |
$11,924 2,347 MMBtu |
$(-382) - $ |
$43 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $5,008 Cost: $6,344 |
$4,624 | 65,763 | $723 | 147 | - | - | $(-382) | - | $43 | - | $4,624 65,763 kWh |
$723 147 kW-months/year |
- - MMBtu |
$(-382) - $ |
$43 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost |