Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | North Carolina State |
---|---|
Assessment Year | 2015 |
Principal Product | Motors |
NAICS | 335312 - Motor and Generator Manufacturing |
SIC | 3621 - Motors And Generators |
Sales | $10,000,000-$50,000,000 |
# of Employees | 100 |
Plant Area (Sq.Ft.) | 270,000 |
Annual Production | 1,800 Pieces |
Production Hrs. Annual | 4,000 |
Location (State) | NC |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $276,360 | 4,424,488 | kWh | $0.06 |
Electricity Demand | $46,406 | 12,542 | kW-months/year | $3.70 |
Natural Gas | $20,387 | 1,995 | MMBtu | $10.22 |
TOTAL ENERGY COSTS | $343,153 | |||
RECOMMENDED SAVINGS* | $41,157 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $1,252 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $17,825 Cost: $50,000 |
$58,742 | 939,872 | $10,433 | 2,820 | $(-51,350) | (-5,000) | - | - | - | - |
$58,742 939,872 kWh |
$10,433 2,820 kW-months/year |
$(-51,350) (-5,000) MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $5,806 Cost: $21,000 |
$5,729 | 91,667 | $4,070 | 1,100 | $(-3,993) | (-391) | - | - | - | - |
$5,729 91,667 kWh |
$4,070 1,100 kW-months/year |
$(-3,993) (-391) MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $2,306 Cost: $1,700 |
$2,306 | 36,900 | - | - | - | - | - | - | - | - |
$2,306 36,900 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $7,255 Cost: $20,000 |
$6,155 | 98,472 | $1,100 | 297 | - | - | - | - | - | - |
$6,155 98,472 kWh |
$1,100 297 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $828 Cost: $100 |
$839 | 13,428 | $149 | 41 | - | - | $(-100) | - | $(-60) | - |
$839 13,428 kWh |
$149 41 kW-months/year |
- - MMBtu |
$(-100) - $ |
$(-60) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $5,230 Cost: $1,875 |
$4,050 | 64,800 | $719 | 194 | - | - | - | - | $461 | - |
$4,050 64,800 kWh |
$719 194 kW-months/year |
- - MMBtu |
- - $ |
$461 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $424 Cost: $1,767 |
$424 | 6,763 | - | - | - | - | - | - | - | - |
$424 6,763 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $1,483 Cost: $4,256 |
$1,259 | 20,148 | $224 | 60 | - | - | - | - | - | - |
$1,259 20,148 kWh |
$224 60 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $41,157 Cost: $100,698 |
$79,504 | 1,272,050 | $16,695 | 4,512 | $(-55,343) | (-5,391) | $(-100) | - | $401 | - | $79,504 1,272,050 kWh |
$16,695 4,512 kW-months/year |
$(-55,343) (-5,391) MMBtu |
$(-100) - $ |
$401 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $1,252 Cost: $1,867 |
$1,263 | 20,191 | $149 | 41 | - | - | $(-100) | - | $(-60) | - | $1,263 20,191 kWh |
$149 41 kW-months/year |
- - MMBtu |
$(-100) - $ |
$(-60) - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Ancillary Material Cost |