Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Oklahoma State University |
---|---|
Assessment Year | 2014 |
Principal Product | Aircraft Parts |
NAICS | 336411 - Aircraft Manufacturing |
SIC | 3721 - Aircraft |
Sales | $100,000,000-$500,000,000 |
# of Employees | 115 |
Plant Area (Sq.Ft.) | 77,860 |
Annual Production | 28,000 Pieces |
Production Hrs. Annual | 8,760 |
Location (State) | KS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $186,385 | 3,522,600 | kWh | $0.05 |
Electricity Demand | $66,383 | 6,006 | kW-months/year | $11.05 |
Natural Gas | $20,148 | 2,960 | MMBtu | $6.81 |
TOTAL ENERGY COSTS | $272,916 | |||
RECOMMENDED SAVINGS* | $73,604 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $73,604 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $36,397 Cost: $35,374 |
$30,148 | 569,908 | $6,249 | 565 | - | - |
$30,148 569,908 kWh |
$6,249 565 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $7,219 Cost: $3,969 |
$7,219 | 136,459 | - | - | - | - |
$7,219 136,459 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7141 LOWER LIGHT FIXTURES IN HIGH CEILING AREAS |
Savings: $8,717 Cost: $3,613 |
$6,775 | 128,071 | $1,942 | 175 | - | - |
$6,775 128,071 kWh |
$1,942 175 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,814 Cost: $8,926 |
$1,814 | 34,286 | - | - | - | - |
$1,814 34,286 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,474 Cost: $11,975 |
$3,474 | 65,667 | - | - | - | - |
$3,474 65,667 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $13,990 Cost: - |
$6,036 | 114,097 | - | - | $7,954 | 1,168 |
$6,036 114,097 kWh |
- - kW-months/year |
$7,954 1,168 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS |
Savings: $1,993 Cost: - |
- | - | $1,993 | 180 | - | - |
- - kWh |
$1,993 180 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $73,604 Cost: $63,857 |
$55,466 | 1,048,488 | $10,184 | 920 | $7,954 | 1,168 | $55,466 1,048,488 kWh |
$10,184 920 kW-months/year |
$7,954 1,168 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $73,604 Cost: $63,857 |
$55,466 | 1,048,488 | $10,184 | 920 | $7,954 | 1,168 | $55,466 1,048,488 kWh |
$10,184 920 kW-months/year |
$7,954 1,168 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||