Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Oregon State University |
---|---|
Assessment Year | 2006 |
Principal Product | Laundry Equipment |
NAICS | 333318 - Other Commercial and Service Industry Machinery Manufacturing |
SIC | 3582 - Commercial Laundry Equipment |
Sales | $1,000,000-$5,000,000 |
# of Employees | 36 |
Plant Area (Sq.Ft.) | 50,000 |
Annual Production | 80 Pieces |
Production Hrs. Annual | 2,000 |
Location (State) | WA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $40,433 | 734,080 | kWh | $0.06 |
Electricity Demand | $10,254 | 3,347 | kW-months/year | $3.06 |
Electricity Fees | $2,861 | - | $ | - |
Natural Gas | $32,976 | 3,759 | MMBtu | $8.77 |
TOTAL ENERGY COSTS | $86,524 | |||
RECOMMENDED SAVINGS* | $21,950 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $19,200 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2514 COVER OPEN TANKS |
Savings: $7,300 Cost: $3,600 |
$7,300 | 132,000 | - | - | - | - | - | - |
$7,300 132,000 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.1113 REDUCE COMBUSTION AIR FLOW TO OPTIMUM |
Savings: $1,300 Cost: - |
- | - | - | - | $1,300 | 125 | - | - |
- - kWh |
- - kW-months/year |
$1,300 125 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,300 Cost: $2,300 |
$1,800 | 32,000 | $500 | 16 | - | - | - | - |
$1,800 32,000 kWh |
$500 16 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $1,450 Cost: $1,800 |
$1,250 | 22,900 | $200 | 6 | - | - | - | - |
$1,250 22,900 kWh |
$200 6 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.1231 ESTABLISH BURNER MAINTENANCE SCHEDULE FOR BOILERS |
Savings: $600 Cost: $400 |
- | - | - | - | $600 | 60 | - | - |
- - kWh |
- - kW-months/year |
$600 60 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $5,400 Cost: $20,000 |
$4,300 | 78,000 | $1,100 | 34 | - | - | - | - |
$4,300 78,000 kWh |
$1,100 34 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $3,600 Cost: $17,400 |
$2,850 | 51,740 | $650 | 20 | - | - | $100 | - |
$2,850 51,740 kWh |
$650 20 kW-months/year |
- - MMBtu |
$100 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $21,950 Cost: $45,500 |
$17,500 | 316,640 | $2,450 | 76 | $1,900 | 185 | $100 | - | $17,500 316,640 kWh |
$2,450 76 kW-months/year |
$1,900 185 MMBtu |
$100 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $19,200 Cost: $43,700 |
$16,250 | 293,740 | $2,250 | 70 | $600 | 60 | $100 | - | $16,250 293,740 kWh |
$2,250 70 kW-months/year |
$600 60 MMBtu |
$100 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |