Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Oregon State University |
---|---|
Assessment Year | 2009 |
Principal Product | Dimensional Lumber, Specialty order Lumber and Beams |
NAICS | 321113 - Sawmills |
SIC | 2421 - Sawmills And Planing Mills, General |
Sales | $10,000,000-$50,000,000 |
# of Employees | 60 |
Plant Area (Sq.Ft.) | 100,000 |
Annual Production | 20,000 Thousand Feet |
Production Hrs. Annual | 2,080 |
Location (State) | OR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $129,750 | 3,074,720 | kWh | $0.04 |
Electricity Demand | $72,095 | 15,943 | kW-months/year | $4.52 |
Electricity Fees | $29,714 | - | $ | - |
Wood | $195,000 | 171,600 | MMBtu | $1.14 |
TOTAL ENERGY COSTS | $426,559 | |||
RECOMMENDED SAVINGS* | $167,848 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $77,108 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Wood | Electricity Usage | Electricity Demand | Electricity Fees | Wood | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1336 INSTALL EQUIPMENT TO UTILIZE WASTE FUEL |
Savings: $90,740 Cost: $81,950 |
- | - | - | - | - | - | $90,740 | 90,948 |
- - kWh |
- - kW-months/year |
- - $ |
$90,740 90,948 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.1232 KEEP BOILER TUBES CLEAN |
Savings: $39,218 Cost: $44,000 |
- | - | - | - | - | - | $39,218 | 12,526 |
- - kWh |
- - kW-months/year |
- - $ |
$39,218 12,526 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $939 Cost: $1,042 |
- | - | - | - | - | - | $939 | 824 |
- - kWh |
- - kW-months/year |
- - $ |
$939 824 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4323 USE OPTIMUM SIZE AND CAPACITY EQUIPMENT |
Savings: $705 Cost: - |
$705 | 16,000 | - | - | - | - | - | - |
$705 16,000 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $5,091 Cost: $5,000 |
$3,305 | 75,000 | $1,786 | 33 | - | - | - | - |
$3,305 75,000 kWh |
$1,786 33 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $16,829 Cost: $20,313 |
$11,943 | 271,853 | $4,886 | 70 | - | - | - | - |
$11,943 271,853 kWh |
$4,886 70 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $4,257 Cost: $500 |
$3,627 | 85,000 | $630 | 12 | - | - | - | - |
$3,627 85,000 kWh |
$630 12 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $1,090 Cost: $500 |
$1,090 | 22,815 | - | - | - | - | - | - |
$1,090 22,815 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.8112 COMBINE UTILITY METERS |
Savings: $6,709 Cost: - |
- | - | - | - | $6,709 | - | - | - |
- - kWh |
- - kW-months/year |
$6,709 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $2,270 Cost: $15,676 |
$2,270 | 33,072 | - | - | - | - | - | - |
$2,270 33,072 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $167,848 Cost: $168,981 |
$22,940 | 503,740 | $7,302 | 115 | $6,709 | - | $130,897 | 104,298 | $22,940 503,740 kWh |
$7,302 115 kW-months/year |
$6,709 - $ |
$130,897 104,298 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $77,108 Cost: $87,031 |
$22,940 | 503,740 | $7,302 | 115 | $6,709 | - | $40,157 | 13,350 | $22,940 503,740 kWh |
$7,302 115 kW-months/year |
$6,709 - $ |
$40,157 13,350 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Wood | Electricity Usage | Electricity Demand | Electricity Fees | Wood |