Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Diego State University |
---|---|
Assessment Year | 2006 |
Principal Product | bread |
NAICS | 311812 - Commercial Bakeries |
SIC | 2051 - Bread, Cake, And Related Products |
Sales | $10,000,000-$50,000,000 |
# of Employees | 150 |
Plant Area (Sq.Ft.) | 110,000 |
Annual Production | 24,000,000 Pieces |
Production Hrs. Annual | 6,240 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $325,635 | 5,051,240 | kWh | $0.06 |
Electricity Demand | $163,336 | 8,037 | kW-months/year | $20.32 |
Natural Gas | $708,553 | 69,652 | MMBtu | $10.17 |
TOTAL ENERGY COSTS | $1,197,524 | |||
RECOMMENDED SAVINGS* | $228,035 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $29,783 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT |
Savings: $171,093 Cost: $182,800 |
$183,933 | 2,851,680 | $111,435 | 5,484 | $(-99,024) | (-9,734) | $(-25,251) | - |
$183,933 2,851,680 kWh |
$111,435 5,484 kW-months/year |
$(-99,024) (-9,734) MMBtu |
$(-25,251) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $20,435 Cost: $42,808 |
$14,263 | 221,126 | $6,172 | 304 | - | - | - | - |
$14,263 221,126 kWh |
$6,172 304 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $14,632 Cost: $13,345 |
- | - | - | - | $14,632 | 1,438 | - | - |
- - kWh |
- - kW-months/year |
$14,632 1,438 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $9,145 Cost: $1,404 |
$3,354 | 52,014 | $5,791 | 285 | - | - | - | - |
$3,354 52,014 kWh |
$5,791 285 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $3,469 Cost: $6,600 |
$2,250 | 87,176 | $1,219 | 140 | - | - | - | - |
$2,250 87,176 kWh |
$1,219 140 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $3,452 Cost: $168 |
$3,452 | 53,533 | - | - | - | - | - | - |
$3,452 53,533 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,382 Cost: $120 |
$2,366 | 36,691 | $1,016 | 50 | - | - | - | - |
$2,366 36,691 kWh |
$1,016 50 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,427 Cost: $5,265 |
$1,696 | 26,295 | $731 | 36 | - | - | - | - |
$1,696 26,295 kWh |
$731 36 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $228,035 Cost: $252,510 |
$211,314 | 3,328,515 | $126,364 | 6,299 | $(-84,392) | (-8,296) | $(-25,251) | - | $211,314 3,328,515 kWh |
$126,364 6,299 kW-months/year |
$(-84,392) (-8,296) MMBtu |
$(-25,251) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $29,783 Cost: $54,841 |
$21,661 | 388,130 | $8,122 | 480 | - | - | - | - | $21,661 388,130 kWh |
$8,122 480 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |