Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Diego State University |
---|---|
Assessment Year | 2016 |
Principal Product | Plastic Film & Packaging |
NAICS | 325211 - Plastics Material and Resin Manufacturing |
SIC | 3089 - Plastics Products, Nec |
Sales | $50,000,000-$100,000,000 |
# of Employees | 300 |
Plant Area (Sq.Ft.) | 270,000 |
Annual Production | 35,000,000 Pounds |
Production Hrs. Annual | 8,760 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,553,414 | 20,509,034 | kWh | $0.08 |
Electricity Demand | $981,385 | 41,040 | kW-months/year | $23.91 |
Electricity Fees | $43,489 | - | $ | - |
Natural Gas | $173,185 | 30,247 | MMBtu | $5.73 |
TOTAL ENERGY COSTS | $2,751,473 | |||
RECOMMENDED SAVINGS* | $483,459 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $356,950 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $324,317 Cost: $112,783 |
$27,638 | 365,102 | $15,187 | 634 | - | - | - | - | $281,492 | - |
$27,638 365,102 kWh |
$15,187 634 kW-months/year |
- - $ |
- - MMBtu |
$281,492 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT |
Savings: $110,770 Cost: $402,000 |
$92,707 | 1,664,400 | $54,515 | 2,280 | - | - | $(-36,452) | (-6,373) | - | - |
$92,707 1,664,400 kWh |
$54,515 2,280 kW-months/year |
- - $ |
$(-36,452) (-6,373) MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $25,449 Cost: $42,926 |
$17,657 | 233,245 | $7,792 | 326 | - | - | - | - | - | - |
$17,657 233,245 kWh |
$7,792 326 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $9,321 Cost: $3,181 |
- | - | - | - | $9,321 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$9,321 - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $7,184 Cost: $6,400 |
$7,184 | 94,902 | - | - | - | - | - | - | - | - |
$7,184 94,902 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $5,708 Cost: $200 |
$5,708 | 75,409 | - | - | - | - | - | - | - | - |
$5,708 75,409 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2693 USE WASTE HEAT STEAM FOR ABSORPTION REFRIGERATION |
Savings: $710 Cost: $3,100 |
$495 | 6,535 | $215 | 9 | - | - | - | - | - | - |
$495 6,535 kWh |
$215 9 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $483,459 Cost: $570,590 |
$151,389 | 2,439,593 | $77,709 | 3,249 | $9,321 | - | $(-36,452) | (-6,373) | $281,492 | - | $151,389 2,439,593 kWh |
$77,709 3,249 kW-months/year |
$9,321 - $ |
$(-36,452) (-6,373) MMBtu |
$281,492 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $356,950 Cost: $162,109 |
$52,479 | 693,249 | $22,979 | 960 | - | - | - | - | $281,492 | - | $52,479 693,249 kWh |
$22,979 960 kW-months/year |
- - $ |
- - MMBtu |
$281,492 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | One-time Revenue or Avoided Cost |