Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Diego State University |
---|---|
Assessment Year | 2025 |
Principal Product | Metal Treatment |
NAICS | 332811 - Metal Heat Treating |
SIC | 3398 - Metal Heat Treating |
Sales | $5,000,000-$10,000,000 |
# of Employees | 34 |
Plant Area (Sq.Ft.) | 64,000 |
Annual Production | 400 Units |
Production Hrs. Annual | 3,188 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $586,685 | 3,704,765 | kWh | $0.16 |
Electricity Demand | $734,855 | 12,932 | kW-months/year | $56.82 |
Electricity Fees | $(-535,389) | - | $ | - |
TOTAL ENERGY COSTS | $786,151 | |||
RECOMMENDED SAVINGS* | $513,478 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Primary Raw Material | Electricity Usage | Electricity Demand | Electricity Fees | Primary Raw Material | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $35,908 Cost: $47,771 |
$14,674 | 92,642 | $21,234 | 374 | - | - | - | - |
$14,674 92,642 kWh |
$21,234 374 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3141 USE BATTERY STORAGE FOR DEMAND CONTROL |
Savings: $109,396 Cost: $5,254 |
$(-6,370) | (-40,212) | $115,766 | 2,037 | - | - | - | - |
$(-6,370) (-40,212) kWh |
$115,766 2,037 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $2,618 Cost: $1,911 |
$1,114 | 7,032 | $1,504 | 26 | - | - | - | - |
$1,114 7,032 kWh |
$1,504 26 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $39,510 Cost: $44,993 |
$31,109 | 196,395 | $8,401 | 148 | - | - | - | - |
$31,109 196,395 kWh |
$8,401 148 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,805 Cost: - |
$1,805 | 11,397 | - | - | - | - | - | - |
$1,805 11,397 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $13,821 Cost: $7,047 |
$5,880 | 37,119 | $7,941 | 140 | - | - | - | - |
$5,880 37,119 kWh |
$7,941 140 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $1,684 Cost: $2,699 |
$1,315 | 8,300 | $369 | 7 | - | - | - | - |
$1,315 8,300 kWh |
$369 7 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $143,491 Cost: - |
- | - | - | - | $143,491 | - | - | - |
- - kWh |
- - kW-months/year |
$143,491 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $153,587 Cost: $200,000 |
- | - | - | - | - | - | $153,587 | - |
- - kWh |
- - kW-months/year |
- - $ |
$153,587 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $9,179 Cost: $8,868 |
$6,455 | 40,748 | $2,724 | 48 | - | - | - | - |
$6,455 40,748 kWh |
$2,724 48 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.4225 INSTALL COMMON HEADER ON COMPRESSORS |
Savings: $2,478 Cost: $2,050 |
$1,326 | 8,368 | $1,153 | 20 | - | - | - | - |
$1,326 8,368 kWh |
$1,153 20 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $513,478 Cost: $320,593 |
$57,307 | 361,789 | $159,093 | 2,800 | $143,491 | - | $153,587 | - | $57,307 361,789 kWh |
$159,093 2,800 kW-months/year |
$143,491 - $ |
$153,587 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Primary Raw Material | Electricity Usage | Electricity Demand | Electricity Fees | Primary Raw Material |