Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Francisco State University
Assessment Year 1999
Principal Product Packaging Film
NAICS n/a
SIC 3081 - Unsupported Plastics Film & Sheet
Sales $10,000,000-$50,000,000
# of Employees 48
Plant Area (Sq.Ft.) 37,500
Annual Production 25,000,000 Pounds
Production Hrs. Annual 8,736
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $388,356 8,458,089 kWh $0.05
Electricity Demand $152,054 13,648 kW-months/year $11.14
Natural Gas $8,548 1,254 MMBtu $6.82
TOTAL ENERGY COSTS $557,629
RECOMMENDED SAVINGS* $24,112 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $2,120
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz)
$ kWh $ kW-months/year $ MMBtu $ lb
01: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$5,214
Cost:
$1,519
$3,942 85,873 $1,272 118 - - - - $3,942
85,873
kWh
$1,272
118
kW-months/year
-
-
MMBtu
-
-
lb
02: 2.2511 INSULATE BARE EQUIPMENT Savings:
$1,742
Cost:
$800
- - - - $1,742 88 - - -
-
kWh
-
-
kW-months/year
$1,742
88
MMBtu
-
-
lb
03: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING Savings:
$6,079
Cost:
$5,335
$4,553 99,062 $1,526 137 - - - - $4,553
99,062
kWh
$1,526
137
kW-months/year
-
-
MMBtu
-
-
lb
04: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$1,303
Cost:
$1,141
$977 21,395 $326 29 - - - - $977
21,395
kWh
$326
29
kW-months/year
-
-
MMBtu
-
-
lb
05: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$756
Cost:
$1,008
$516 11,137 $240 22 - - - - $516
11,137
kWh
$240
22
kW-months/year
-
-
MMBtu
-
-
lb
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$8,640
Cost:
$22,110
$5,777 125,733 $2,863 257 - - - - $5,777
125,733
kWh
$2,863
257
kW-months/year
-
-
MMBtu
-
-
lb
07: 3.5313 INCREASE AMOUNT OF WASTE RECOVERED FOR RESALE Savings:
$378
Cost:
-
- - - - - - $378 - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$378
-
lb
TOTAL RECOMMENDED Savings:
$24,112
Cost:
$31,913
$15,765 343,200 $6,227 563 $1,742 88 $378 - $15,765
343,200
kWh
$6,227
563
kW-months/year
$1,742
88
MMBtu
$378
-
lb
TOTAL IMPLEMENTED Savings:
$2,120
Cost:
$800
- - - - $1,742 88 $378 - -
-
kWh
-
-
kW-months/year
$1,742
88
MMBtu
$378
-
lb
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ lb
Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz) Electricity Usage Electricity Demand Natural Gas Solid Waste (non-haz)