Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Francisco State University |
---|---|
Assessment Year | 2004 |
Principal Product | Chocolate Product |
NAICS | 311351 - Chocolate and Confectionery Manufacturing from Cacao Beans |
SIC | 2066 - Chocolate And Cocoa Products |
Sales | $10,000,000-$50,000,000 |
# of Employees | 120 |
Plant Area (Sq.Ft.) | 120,000 |
Annual Production | 0 Pounds |
Production Hrs. Annual | 7,488 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $598,829 | 5,317,200 | kWh | $0.11 |
Electricity Demand | $158,948 | 12,496 | kW-months/year | $12.72 |
Natural Gas | $65,612 | 8,170 | MMBtu | $8.03 |
TOTAL ENERGY COSTS | $906,034 | |||
RECOMMENDED SAVINGS* | $99,214 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $57,941 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Electricity Fees | Solid Waste (non-haz) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | lb | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $14,198 Cost: - |
$14,198 | 126,072 | - | - | - | - | - | - |
$14,198 126,072 kWh |
- - kW-months/year |
- - $ |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2111 INSTALL STEAM TRAP |
Savings: $1,304 Cost: $299 |
$1,104 | 9,804 | $200 | 16 | - | - | - | - |
$1,104 9,804 kWh |
$200 16 kW-months/year |
- - $ |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $7,053 Cost: $2,417 |
$5,919 | 52,564 | $1,134 | 89 | - | - | - | - |
$5,919 52,564 kWh |
$1,134 89 kW-months/year |
- - $ |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $2,015 Cost: $1,440 |
$1,752 | 15,557 | $263 | 21 | - | - | - | - |
$1,752 15,557 kWh |
$263 21 kW-months/year |
- - $ |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $10,516 Cost: $14,960 |
$8,905 | 79,073 | $1,611 | 127 | - | - | - | - |
$8,905 79,073 kWh |
$1,611 127 kW-months/year |
- - $ |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $272 Cost: $571 |
$216 | 1,920 | $56 | 4 | - | - | - | - |
$216 1,920 kWh |
$56 4 kW-months/year |
- - $ |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $442 Cost: $1,200 |
$274 | 2,433 | $168 | 13 | - | - | - | - |
$274 2,433 kWh |
$168 13 kW-months/year |
- - $ |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $2,037 Cost: $5,155 |
$1,868 | 16,548 | $169 | 13 | - | - | - | - |
$1,868 16,548 kWh |
$169 13 kW-months/year |
- - $ |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $2,517 Cost: $8,685 |
$2,135 | 18,960 | $382 | 31 | - | - | - | - |
$2,135 18,960 kWh |
$382 31 kW-months/year |
- - $ |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 3.2111 INSTALL REDUNDANT EQUIPMENT TO AVOID LOSSES CAUSED BY EQUIPMENT FAILURE AND ROUTINE MAINTENANCE |
Savings: $34,944 Cost: $72 |
- | - | - | - | - | - | $34,944 | - |
- - kWh |
- - kW-months/year |
- - $ |
$34,944 - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 3.6193 INSTALL EQUIPMENT (eg COMPACTOR) TO REDUCE DISPOSAL COSTS |
Savings: $20,271 Cost: $21,650 |
- | - | - | - | - | - | $20,271 | - |
- - kWh |
- - kW-months/year |
- - $ |
$20,271 - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $3,645 Cost: $2,914 |
- | - | - | - | $3,645 | - | - | - |
- - kWh |
- - kW-months/year |
$3,645 - $ |
- - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $99,214 Cost: $59,363 |
$36,371 | 322,931 | $3,983 | 314 | $3,645 | - | $55,215 | - | $36,371 322,931 kWh |
$3,983 314 kW-months/year |
$3,645 - $ |
$55,215 - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $57,941 Cost: $3,988 |
$21,495 | 190,873 | $1,502 | 118 | - | - | $34,944 | - | $21,495 190,873 kWh |
$1,502 118 kW-months/year |
- - $ |
$34,944 - lb |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | lb | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Electricity Fees | Solid Waste (non-haz) |