Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Francisco State University |
---|---|
Assessment Year | 2005 |
Principal Product | raisins |
NAICS | 311423 - Dried and Dehydrated Food Manufacturing |
SIC | 2034 - Dehydrated Fruits, Vegetables, Soups |
Sales | $10,000,000-$50,000,000 |
# of Employees | 48 |
Plant Area (Sq.Ft.) | 39,000 |
Annual Production | 20,000 Tons |
Production Hrs. Annual | 3,336 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $157,370 | 1,779,211 | kWh | $0.09 |
Electricity Demand | $60,804 | 5,927 | kW-months/year | $10.26 |
Natural Gas | $50,567 | 5,718 | MMBtu | $8.84 |
TOTAL ENERGY COSTS | $268,741 | |||
RECOMMENDED SAVINGS* | $51,632 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $15,177 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1231 ESTABLISH BURNER MAINTENANCE SCHEDULE FOR BOILERS |
Savings: $4,353 Cost: - |
- | - | - | - | $4,353 | 575 | - | - |
- - kWh |
- - kW-months/year |
$4,353 575 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $6,788 Cost: - |
- | - | - | - | $6,788 | 148 | - | - |
- - kWh |
- - kW-months/year |
$6,788 148 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $258 Cost: - |
$258 | 6,229 | - | - | - | - | - | - |
$258 6,229 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $1,926 Cost: $807 |
- | - | - | - | $1,926 | 226 | - | - |
- - kWh |
- - kW-months/year |
$1,926 226 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $10,186 Cost: $14,112 |
$7,162 | 79,995 | $3,024 | 282 | - | - | - | - |
$7,162 79,995 kWh |
$3,024 282 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE |
Savings: $20,484 Cost: $30,250 |
- | - | - | - | - | - | $20,484 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$20,484 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $1,127 Cost: $2,564 |
$554 | 6,139 | $573 | 53 | - | - | - | - |
$554 6,139 kWh |
$573 53 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS |
Savings: $2,436 Cost: $5,848 |
$1,566 | 17,492 | $870 | 81 | - | - | - | - |
$1,566 17,492 kWh |
$870 81 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $1,342 Cost: $4,848 |
$576 | 6,438 | $766 | 71 | - | - | - | - |
$576 6,438 kWh |
$766 71 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $447 Cost: $2,408 |
$447 | 4,998 | - | - | - | - | - | - |
$447 4,998 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 3.1162 USE LESS WASTEFUL PACKAGING |
Savings: $2,285 Cost: - |
- | - | - | - | - | - | $2,285 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$2,285 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $51,632 Cost: $60,837 |
$10,563 | 121,291 | $5,233 | 487 | $13,067 | 949 | $22,769 | - | $10,563 121,291 kWh |
$5,233 487 kW-months/year |
$13,067 949 MMBtu |
$22,769 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $15,177 Cost: $10,696 |
$2,400 | 30,159 | $1,636 | 152 | $11,141 | 723 | - | - | $2,400 30,159 kWh |
$1,636 152 kW-months/year |
$11,141 723 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost |