Select a Center

Arizona State University
Boise State University
Case Western Reserve University
Clemson University
Colorado State University
Georgia Institute of Technology
Indiana University-Purdue University
Lehigh University
Louisiana State University
North Carolina State
Oklahoma State University
Oregon State University
San Diego State University
San Francisco State University
Syracuse University
Tennessee Technological University
Texas A&M, College Station
University of Alabama
University of Dayton
University of Delaware
University of Florida
University of Illinois, Chicago
University of Kentucky
University of Massachusetts
University of Miami
University of Missouri-Columbia
University of Nebraska–Lincoln
University of Texas Rio Grande Valley
University of Utah
University of Wisconsin, Milwaukee
West Virginia University
IAC logo
IAC Assessment: SF0366
Sponsored by:
EERE AMO
IAC logo
IAC Assessment: SF0366
Due to University and State restrictions around the country, all IAC assessment activities are temporarily on hold.
Click here for details about Coronavirus (COVID-19) Recovery Support programs
IAC Center San Francisco State University
Assessment Year 2008
Principal Product Building Supply
NAICS 321918 - Other Millwork (including Flooring)
SIC 2431 - Millwork
Sales $25,000,000
# of Employees 72
Plant Area (Sq.Ft.) 54,000
Annual Production 1 Pieces
Production Hrs. Annual 2,860
Location (State) HI
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $197,789 544,920 kWh $0.36
Electricity Demand $21,477 3,068 kW/month $7.00
Electricity Fees $86,177 - $ -
Other Gas $19,513 944 MMBtu $20.67
TOTAL ENERGY COSTS $324,956
RECOMMENDED SAVINGS* $28,186 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $16,905
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW/month
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$10,775
Cost:
-
$10,775 37,928 - - $10,775
37,928
kWh
-
-
kW/month
02: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED Savings:
$4,455
Cost:
$452
$4,455 14,303 - - $4,455
14,303
kWh
-
-
kW/month
03: 2.4133 USE MOST EFFICIENT TYPE OF ELECTRIC MOTORS Savings:
$3,202
Cost:
$1,339
$2,867 9,946 $335 48 $2,867
9,946
kWh
$335
48
kW/month
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$176
Cost:
$93
$151 503 $25 4 $151
503
kWh
$25
4
kW/month
05: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED Savings:
$2,839
Cost:
$2,119
$2,839 9,847 - - $2,839
9,847
kWh
-
-
kW/month
06: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED Savings:
$2,476
Cost:
$2,404
$2,476 8,587 - - $2,476
8,587
kWh
-
-
kW/month
07: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$3,134
Cost:
$4,709
$3,036 9,843 $98 14 $3,036
9,843
kWh
$98
14
kW/month
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$853
Cost:
$2,892
$853 2,958 - - $853
2,958
kWh
-
-
kW/month
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$276
Cost:
$953
$251 220 $25 4 $251
220
kWh
$25
4
kW/month
TOTAL RECOMMENDED Savings:
$28,186
Cost:
$14,961
$27,703 94,135 $483 70 $27,703
94,135
kWh
$483
70
kW/month
TOTAL IMPLEMENTED Savings:
$16,905
Cost:
$4,789
$16,520 57,184 $385 56 $16,520
57,184
kWh
$385
56
kW/month
Savings
Cost
$ kWh $ kW/month
Electricity Usage Electricity Demand Electricity Usage Electricity Demand