Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Francisco State University
Assessment Year 2018
Principal Product Food Pudding
NAICS 311514 - Dry, Condensed, and Evaporated Dairy Product Manufacturing
SIC 2026 - Fluid Milk
Sales $50,000,000-$100,000,000
# of Employees 107
Plant Area (Sq.Ft.) 78,000
Annual Production 30,500,000 Pounds
Production Hrs. Annual 6,660
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $294,094 3,103,238 kWh $0.09
Electricity Demand $97,754 8,626 kW-months/year $11.33
Natural Gas $109,465 11,484 MMBtu $9.53
TOTAL ENERGY COSTS $501,313
RECOMMENDED SAVINGS* $130,136 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $44,149
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Personnel Changes Primary Raw Material Electricity Usage Electricity Demand Natural Gas Personnel Changes Primary Raw Material
$ kWh $ kW-months/year $ MMBtu $ $ $ $
01: 2.6214 SHUT OFF PILOTS IN STANDBY EQUIPMENT Savings:
$3,418
Cost:
$136
$55 580 - - $3,363 353 - - - - $55
580
kWh
-
-
kW-months/year
$3,363
353
MMBtu
-
-
$
-
-
$
02: 2.2694 USE HIGHEST TEMPERATURE FOR CHILLING OR COLD STORAGE Savings:
$7,652
Cost:
$800
$6,575 69,382 $1,077 95 - - - - - - $6,575
69,382
kWh
$1,077
95
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
03: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,563
Cost:
$136
$2,136 22,540 $427 38 - - - - - - $2,136
22,540
kWh
$427
38
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
04: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES Savings:
$4,469
Cost:
$4,039
- - - - $4,469 469 - - - - -
-
kWh
-
-
kW-months/year
$4,469
469
MMBtu
-
-
$
-
-
$
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$8,296
Cost:
$8,179
$6,843 72,212 $1,797 159 - - $188 - $(-532) - $6,843
72,212
kWh
$1,797
159
kW-months/year
-
-
MMBtu
$188
-
$
$(-532)
-
$
06: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$942
Cost:
$900
$942 9,944 - - - - - - - - $942
9,944
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
07: 2.2621 MODIFY REFRIGERATION SYSTEM TO OPERATE AT A LOWER PRESSURE Savings:
$17,938
Cost:
$24,858
$17,938 189,277 - - - - - - - - $17,938
189,277
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
08: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$82,569
Cost:
$631,513
$74,168 782,612 $8,401 742 - - - - - - $74,168
782,612
kWh
$8,401
742
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
09: 2.3132 RECHARGE BATTERIES ON DURING OFF-PEAK DEMAND PERIODS Savings:
$2,289
Cost:
$953
- - $2,289 202 - - - - - - -
-
kWh
$2,289
202
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
TOTAL RECOMMENDED Savings:
$130,136
Cost:
$671,514
$108,657 1,146,547 $13,991 1,235 $7,832 822 $188 - $(-532) - $108,657
1,146,547
kWh
$13,991
1,235
kW-months/year
$7,832
822
MMBtu
$188
-
$
$(-532)
-
$
TOTAL IMPLEMENTED Savings:
$44,149
Cost:
$39,865
$34,434 363,355 $5,590 493 $4,469 469 $188 - $(-532) - $34,434
363,355
kWh
$5,590
493
kW-months/year
$4,469
469
MMBtu
$188
-
$
$(-532)
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $ $ $
Electricity Usage Electricity Demand Natural Gas Personnel Changes Primary Raw Material Electricity Usage Electricity Demand Natural Gas Personnel Changes Primary Raw Material