Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Francisco State University |
---|---|
Assessment Year | 2021 |
Principal Product | Treated Water |
NAICS | 221320 - Sewage Treatment Facilities |
SIC | 4952 - Sewerage Systems |
Sales | $5,000,000-$10,000,000 |
# of Employees | 10 |
Plant Area (Sq.Ft.) | 652,200 |
Annual Production | 1,100,000 Thousand Gallons |
Production Hrs. Annual | 8,760 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $422,235 | 4,114,377 | kWh | $0.10 |
Electricity Demand | $176,833 | 5,988 | kW-months/year | $29.53 |
TOTAL ENERGY COSTS | $630,068 | |||
RECOMMENDED SAVINGS* | $413,825 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Solid Waste (haz) | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Solid Waste (haz) | Personnel Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | lb | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $8,567 Cost: - |
- | - | $8,129 | 854 | $438 | - | - | - | - | - | - | - |
- - kWh |
$8,129 854 kW-months/year |
$438 - $ |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $72,559 Cost: $11,960 |
$54,950 | 535,418 | $17,609 | 587 | - | - | - | - | - | - | - | - |
$54,950 535,418 kWh |
$17,609 587 kW-months/year |
- - $ |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $126,207 Cost: $44,180 |
$95,579 | 931,300 | $30,628 | 1,020 | - | - | - | - | - | - | - | - |
$95,579 931,300 kWh |
$30,628 1,020 kW-months/year |
- - $ |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $17,474 Cost: $38,541 |
$10,018 | 97,608 | $5,435 | 181 | - | - | - | - | $1,098 | - | $923 | - |
$10,018 97,608 kWh |
$5,435 181 kW-months/year |
- - $ |
- - lb |
$1,098 - $ |
$923 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.9141 Install Anaerobic Digester |
Savings: $189,018 Cost: $1,222,260 |
$126,296 | 1,230,600 | $36,972 | 1,232 | - | - | $25,750 | 300,000 | - | - | - | - |
$126,296 1,230,600 kWh |
$36,972 1,232 kW-months/year |
- - $ |
$25,750 300,000 lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $413,825 Cost: $1,316,941 |
$286,843 | 2,794,926 | $98,773 | 3,874 | $438 | - | $25,750 | 300,000 | $1,098 | - | $923 | - | $286,843 2,794,926 kWh |
$98,773 3,874 kW-months/year |
$438 - $ |
$25,750 300,000 lb |
$1,098 - $ |
$923 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - $ |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | lb | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||