Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Stevens Institute of Technology
Assessment Year 1985
Principal Product ELECTRICAL CONTROLS
NAICS n/a
SIC 3625 - Relays And Industrial Controls
Sales $5,000,000-$10,000,000
# of Employees 351
Plant Area (Sq.Ft.) 0
Annual Production 1,200,000 Pieces
Production Hrs. Annual 2,023
Location (State) NY
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $311,731 2,498,535 kWh $0.12
TOTAL ENERGY COSTS $311,731
RECOMMENDED SAVINGS* $60,678 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $39,547
#|Description Savings
Cost
Status Electricity Usage Natural Gas Electricity Usage Natural Gas
$ kWh $ MMBtu
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$8,841
Cost:
$13,140
$8,841 70,633 - - $8,841
70,633
kWh
-
-
MMBtu
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$5,014
Cost:
$240
$5,014 40,152 - - $5,014
40,152
kWh
-
-
MMBtu
03: 2.4324 REPLACE HYDRAULIC / PNEUMATIC EQUIPMENT WITH ELECTRIC EQUIPMENT Savings:
$2,300
Cost:
$2,180
$2,300 18,464 - - $2,300
18,464
kWh
-
-
MMBtu
04: 2.6121 REDUCE HOT WATER TEMPERATURE TO THE MINIMUM REQUIRED Savings:
$106
Cost:
-
$106 879 - - $106
879
kWh
-
-
MMBtu
06: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT Savings:
$177
Cost:
$285
$224 1,758 $(-47) (-8) $224
1,758
kWh
$(-47)
(-8)
MMBtu
07: 2.2514 COVER OPEN TANKS Savings:
$475
Cost:
$400
- - $475 75 -
-
kWh
$475
75
MMBtu
08: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS Savings:
$433
Cost:
$700
$(-233) (-2,052) $666 105 $(-233)
(-2,052)
kWh
$666
105
MMBtu
09: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$1,520
Cost:
$537
- - $1,520 241 -
-
kWh
$1,520
241
MMBtu
10: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES Savings:
$3,918
Cost:
$3,089
- - $3,918 619 -
-
kWh
$3,918
619
MMBtu
11: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$1,508
Cost:
$350
- - $1,508 238 -
-
kWh
$1,508
238
MMBtu
12: 2.7421 REDUCE GLAZED AREAS IN BUILDINGS Savings:
$1,130
Cost:
$4,848
- - $1,130 179 -
-
kWh
$1,130
179
MMBtu
13: 2.7441 REPLACE BROKEN WINDOWS AND/OR WINDOW SASH Savings:
$9,670
Cost:
$136
- - $9,670 1,528 -
-
kWh
$9,670
1,528
MMBtu
14: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$25,586
Cost:
$3,500
- - $25,586 4,042 -
-
kWh
$25,586
4,042
MMBtu
TOTAL RECOMMENDED Savings:
$60,678
Cost:
$29,405
$16,252 129,834 $44,426 7,019 $16,252
129,834
kWh
$44,426
7,019
MMBtu
TOTAL IMPLEMENTED Savings:
$39,547
Cost:
$16,880
$13,961 111,664 $25,586 4,042 $13,961
111,664
kWh
$25,586
4,042
MMBtu
Savings
Cost
$ kWh $ MMBtu
Electricity Usage Natural Gas Electricity Usage Natural Gas