Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Syracuse University |
---|---|
Assessment Year | 2005 |
Principal Product | Thick Film Micro-Electronic Components |
NAICS | 334418 - Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3679 - Electronic Components, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 127 |
Plant Area (Sq.Ft.) | 45,000 |
Annual Production | 91,322 Pieces |
Production Hrs. Annual | 4,284 |
Location (State) | NY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $173,621 | 2,023,504 | kWh | $0.09 |
Electricity Demand | $53,139 | 3,904 | kW-months/year | $13.61 |
Electricity Fees | $3,175 | - | $ | - |
Natural Gas | $36,676 | 3,834 | MMBtu | $9.57 |
TOTAL ENERGY COSTS | $266,611 | |||
RECOMMENDED SAVINGS* | $145,934 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $9,200 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 4.821 PAY BILLS ON TIME TO AVOID LATE FEES |
Savings: $395 Cost: - |
- | - | - | - | - | - | $395 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$395 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $3,679 Cost: - |
$3,012 | 33,466 | $667 | 49 | - | - | - | - |
$3,012 33,466 kWh |
$667 49 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4314 USE SYNTHETIC LUBRICANT |
Savings: $375 Cost: - |
$307 | 3,407 | $68 | 5 | - | - | - | - |
$307 3,407 kWh |
$68 5 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $670 Cost: - |
$547 | 6,079 | $123 | 9 | - | - | - | - |
$547 6,079 kWh |
$123 9 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.1222 INSTALL TURBULATORS |
Savings: $985 Cost: $571 |
- | - | - | - | $985 | 103 | - | - |
- - kWh |
- - kW-months/year |
$985 103 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $2,637 Cost: $1,889 |
$2,147 | 23,856 | $490 | 36 | - | - | - | - |
$2,147 23,856 kWh |
$490 36 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2492 USE "HEAT WHEEL" OR OTHER HEAT EXCHANGER TO CROSS-EXCHANGE BUILDING EXHAUST AIR WITH MAKE-UP AIR |
Savings: $12,179 Cost: $10,575 |
- | - | - | - | $12,179 | 1,274 | - | - |
- - kWh |
- - kW-months/year |
$12,179 1,274 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,966 Cost: $2,792 |
$1,966 | 21,840 | - | - | - | - | - | - |
$1,966 21,840 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $230 Cost: $383 |
$189 | 2,097 | $41 | 3 | - | - | - | - |
$189 2,097 kWh |
$41 3 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $148 Cost: $527 |
$148 | 1,643 | - | - | - | - | - | - |
$148 1,643 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7314 REDUCE VENTILATION AIR |
Savings: $3,820 Cost: $13,919 |
$3,738 | 41,539 | $82 | 6 | - | - | - | - |
$3,738 41,539 kWh |
$82 6 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $97,661 Cost: $114,600 |
$60,934 | 677,040 | $12,657 | 930 | $34,903 | (-3,651) | $(-10,833) | - |
$60,934 677,040 kWh |
$12,657 930 kW-months/year |
$34,903 (-3,651) MMBtu |
$(-10,833) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
13: 3.1191 CHANGE PROCEDURES / EQUIPMENT / OPERATING CONDITIONS |
Savings: $21,189 Cost: $111,859 |
- | - | - | - | - | - | $21,189 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$21,189 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $145,934 Cost: $257,115 |
$72,988 | 810,967 | $14,128 | 1,038 | $48,067 | (-2,274) | $10,751 | - | $72,988 810,967 kWh |
$14,128 1,038 kW-months/year |
$48,067 (-2,274) MMBtu |
$10,751 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $9,200 Cost: $5,208 |
$7,580 | 84,212 | $1,225 | 90 | - | - | $395 | - | $7,580 84,212 kWh |
$1,225 90 kW-months/year |
- - MMBtu |
$395 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost |