Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Syracuse University |
---|---|
Assessment Year | 2022 |
Principal Product | Storage and Distribution of food and paper |
NAICS | 493110 - General Warehousing and Storage |
SIC | 4225 - General Warehousing And Storage |
Sales | $100,000,000-$500,000,000 |
# of Employees | 90 |
Plant Area (Sq.Ft.) | 56,000 |
Annual Production | 6,100,000 Units |
Production Hrs. Annual | 8,281 |
Location (State) | NY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $78,294 | 1,559,082 | kWh | $0.05 |
Electricity Demand | $57,966 | 3,391 | kW-months/year | $17.09 |
Electricity Fees | $29,398 | - | $ | - |
Natural Gas | $9,828 | 1,603 | MMBtu | $6.13 |
TOTAL ENERGY COSTS | $175,486 | |||
RECOMMENDED SAVINGS* | $30,203 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7122 DISCONNECT BALLASTS |
Savings: $4,994 Cost: - |
$3,089 | 61,781 | $1,905 | 111 | - | - | - | - |
$3,089 61,781 kWh |
$1,905 111 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $9,899 Cost: $250 |
$5,908 | 118,154 | $3,980 | 233 | - | - | $12 | - |
$5,908 118,154 kWh |
$3,980 233 kW-months/year |
- - MMBtu |
$12 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $659 Cost: $19 |
$252 | 5,040 | $538 | 32 | $(-132) | (-21) | - | - |
$252 5,040 kWh |
$538 32 kW-months/year |
$(-132) (-21) MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS |
Savings: $2,907 Cost: $675 |
- | - | $2,907 | 170 | - | - | - | - |
- - kWh |
$2,907 170 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $652 Cost: $567 |
$652 | 13,032 | - | - | - | - | - | - |
$652 13,032 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $1,859 Cost: $2,600 |
$(-217) | (-4,335) | $(-176) | (-10) | $2,251 | 367 | - | - |
$(-217) (-4,335) kWh |
$(-176) (-10) kW-months/year |
$2,251 367 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES |
Savings: $125 Cost: $325 |
$125 | 2,500 | - | - | - | - | - | - |
$125 2,500 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7314 REDUCE VENTILATION AIR |
Savings: $346 Cost: $1,265 |
$49 | 994 | - | - | $297 | 49 | - | - |
$49 994 kWh |
- - kW-months/year |
$297 49 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $8,763 Cost: $47,904 |
$8,763 | 175,250 | - | - | - | - | - | - |
$8,763 175,250 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $30,203 Cost: $53,605 |
$18,621 | 372,416 | $9,154 | 535 | $2,417 | 394 | $12 | - | $18,621 372,416 kWh |
$9,154 535 kW-months/year |
$2,417 394 MMBtu |
$12 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||