Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Texas, Arlington |
---|---|
Assessment Year | 2002 |
Principal Product | Iron and Steel plug valves |
NAICS | n/a |
SIC | 3494 - Valves And Pipe Fittings, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 211 |
Plant Area (Sq.Ft.) | 307,000 |
Annual Production | 60,000 Pieces |
Production Hrs. Annual | 6,312 |
Location (State) | TX |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $543,826 | 12,951,975 | kWh | $0.04 |
Electricity Demand | $249,692 | 30,138 | kW-months/year | $8.28 |
Electricity Fees | $9,717 | - | $ | - |
Natural Gas | $9,216 | 9,856 | MMBtu | $0.94 |
TOTAL ENERGY COSTS | $820,251 | |||
RECOMMENDED SAVINGS* | $24,763 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $18,988 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Water Disposal | Electricity Usage | Electricity Demand | Water Disposal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $5,615 Cost: $400 |
$4,190 | 121,400 | $1,425 | 121 | - | - |
$4,190 121,400 kWh |
$1,425 121 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $5,600 Cost: $550 |
$3,400 | 98,467 | $2,200 | 187 | - | - |
$3,400 98,467 kWh |
$2,200 187 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 3.7115 CLEAN LINES WITH "PIGS" INSTEAD OF SOLVENTS / SOLUTIONS |
Savings: $4,915 Cost: $750 |
- | - | - | - | $4,915 | 1,575 |
- - kWh |
- - kW-months/year |
$4,915 1,575 Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $2,680 Cost: $635 |
$2,680 | 77,700 | - | - | - | - |
$2,680 77,700 kWh |
- - kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,290 Cost: $440 |
$2,290 | 66,390 | - | - | - | - |
$2,290 66,390 kWh |
- - kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $1,070 Cost: $700 |
$1,070 | 31,082 | - | - | - | - |
$1,070 31,082 kWh |
- - kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4314 USE SYNTHETIC LUBRICANT |
Savings: $858 Cost: - |
$410 | 11,877 | $448 | 38 | - | - |
$410 11,877 kWh |
$448 38 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7122 DISCONNECT BALLASTS |
Savings: $660 Cost: $675 |
$400 | 11,655 | $260 | 22 | - | - |
$400 11,655 kWh |
$260 22 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $560 Cost: $150 |
$560 | 16,285 | - | - | - | - |
$560 16,285 kWh |
- - kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $315 Cost: $640 |
$220 | 6,377 | $95 | 8 | - | - |
$220 6,377 kWh |
$95 8 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME |
Savings: $200 Cost: - |
$200 | 5,780 | - | - | - | - |
$200 5,780 kWh |
- - kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $24,763 Cost: $4,940 |
$15,420 | 447,013 | $4,428 | 376 | $4,915 | 1,575 | $15,420 447,013 kWh |
$4,428 376 kW-months/year |
$4,915 1,575 Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $18,988 Cost: $3,515 |
$14,820 | 429,578 | $4,168 | 354 | - | - | $14,820 429,578 kWh |
$4,168 354 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Water Disposal | Electricity Usage | Electricity Demand | Water Disposal |