Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Texas, Arlington |
---|---|
Assessment Year | 2002 |
Principal Product | Auto Alternators and Brake Pads |
NAICS | n/a |
SIC | 3714 - Motor Vehicle Parts And Accessories |
Sales | $10,000,000-$50,000,000 |
# of Employees | 174 |
Plant Area (Sq.Ft.) | 49,000 |
Annual Production | 800,000 Pieces |
Production Hrs. Annual | 4,518 |
Location (State) | TX |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $63,403 | 1,450,043 | kWh | $0.04 |
Electricity Demand | $41,575 | 4,845 | kW-months/year | $8.58 |
Electricity Fees | $9,325 | - | $ | - |
Natural Gas | $56,364 | 7,212 | MMBtu | $7.82 |
TOTAL ENERGY COSTS | $170,667 | |||
RECOMMENDED SAVINGS* | $30,541 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $29,307 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7231 USE RADIANT HEATER FOR SPOT HEATING |
Savings: $11,011 Cost: $3,255 |
- | - | - | - | - | - | $11,011 | 1,409 |
- - kWh |
- - kW-months/year |
- - $ |
$11,011 1,409 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE |
Savings: $8,422 Cost: - |
- | - | - | - | $8,422 | - | - | - |
- - kWh |
- - kW-months/year |
$8,422 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $5,485 Cost: $6,700 |
$2,961 | 82,101 | $2,524 | 205 | - | - | - | - |
$2,961 82,101 kWh |
$2,524 205 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $2,770 Cost: $476 |
- | - | - | - | - | - | $2,770 | 354 |
- - kWh |
- - kW-months/year |
- - $ |
$2,770 354 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $972 Cost: $212 |
$972 | 26,930 | - | - | - | - | - | - |
$972 26,930 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME |
Savings: $912 Cost: - |
$912 | 25,278 | - | - | - | - | - | - |
$912 25,278 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4314 USE SYNTHETIC LUBRICANT |
Savings: $400 Cost: - |
$200 | 5,634 | $200 | 17 | - | - | - | - |
$200 5,634 kWh |
$200 17 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $307 Cost: $338 |
$307 | 8,510 | - | - | - | - | - | - |
$307 8,510 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7122 DISCONNECT BALLASTS |
Savings: $262 Cost: $49 |
$137 | 3,800 | $125 | 10 | - | - | - | - |
$137 3,800 kWh |
$125 10 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $30,541 Cost: $11,030 |
$5,489 | 152,253 | $2,849 | 232 | $8,422 | - | $13,781 | 1,763 | $5,489 152,253 kWh |
$2,849 232 kW-months/year |
$8,422 - $ |
$13,781 1,763 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $29,307 Cost: $10,769 |
$4,380 | 121,523 | $2,724 | 222 | $8,422 | - | $13,781 | 1,763 | $4,380 121,523 kWh |
$2,724 222 kW-months/year |
$8,422 - $ |
$13,781 1,763 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas |