Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Tennessee
Assessment Year 1991
Principal Product ROUGH-CUT LUMBER
NAICS n/a
SIC 2421 - Sawmills And Planing Mills, General
Sales $1,000,000-$5,000,000
# of Employees 21
Plant Area (Sq.Ft.) 0
Annual Production 12,500 Thousand Feet
Production Hrs. Annual 2,250
Location (State) KY
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $48,102 319,461 kWh $0.15
Natural Gas $12,200 2,634 MMBtu $4.63
Wood $25,000 688,000 MMBtu $0.04
TOTAL ENERGY COSTS $85,302
RECOMMENDED SAVINGS* $244,249 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Natural Gas Electricity Usage Natural Gas
$ kWh $ MMBtu
01: 2.3414 BURN WASTE TO PRODUCE STEAM TO DRIVE A STEAM TURBINE GENERATOR SET AND USE STEAM EXHAUST FOR HEAT Savings:
$224,192
Cost:
-
$211,992 3,597,304 $12,200 2,634 $211,992
3,597,304
kWh
$12,200
2,634
MMBtu
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$5,443
Cost:
$2,415
$5,443 36,049 - - $5,443
36,049
kWh
-
-
MMBtu
03: 2.6211 CONSERVE ENERGY BY EFFICIENT USE OF VENDING MACHINES Savings:
$974
Cost:
$285
$974 6,448 - - $974
6,448
kWh
-
-
MMBtu
04: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME Savings:
$310
Cost:
-
$310 2,052 - - $310
2,052
kWh
-
-
MMBtu
05: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER Savings:
$8,200
Cost:
$13,500
$8,200 - - - $8,200
-
kWh
-
-
MMBtu
06: 2.3131 RESCHEDULE PLANT OPERATIONS OR REDUCE LOAD TO AVOID PEAKS Savings:
$5,130
Cost:
-
$5,130 - - - $5,130
-
kWh
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$244,249
Cost:
$16,200
$232,049 3,641,853 $12,200 2,634 $232,049
3,641,853
kWh
$12,200
2,634
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - -
-
kWh
-
-
MMBtu
Savings
Cost
$ kWh $ MMBtu
Electricity Usage Natural Gas Electricity Usage Natural Gas