IAC Center | University of Tennessee |
---|---|
Assessment Year | 1996 |
Principal Product | Uniform pants and outerwear |
NAICS | n/a |
SIC | 2311 - Men's and Boys' Suits, Coats, and Overcoats |
Sales | $50,000,000-$100,000,000 |
# of Employees | 425 |
Plant Area (Sq.Ft.) | 185,000 |
Annual Production | 28,109,250 Pieces |
Production Hrs. Annual | 3,557 |
Location (State) | TN |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $268,873 | 4,497,069 | kWh | $0.06 |
Electricity Demand | $130,841 | 14,308 | kW-months/year | $9.14 |
Natural Gas | $52,147 | 10,252 | MMBtu | $5.09 |
TOTAL ENERGY COSTS | $1,410,155 | |||
RECOMMENDED SAVINGS* | $169,049 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $18,156 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) | Personnel Changes | By-product Production | Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) | Personnel Changes | By-product Production | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | lb | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 3.5313 INCREASE AMOUNT OF WASTE RECOVERED FOR RESALE |
Savings: $149,480 Cost: $150,000 |
- | - | - | - | - | - | $12,480 | 270,000 | $(-25,000) | - | $162,000 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$12,480 270,000 lb |
$(-25,000) - $ |
$162,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3191 USE DEMAND CONTROLLER OR LOAD SHEDDER |
Savings: $13,909 Cost: $15,800 |
- | - | $13,909 | 1,428 | - | - | - | - | - | - | - | - |
- - kWh |
$13,909 1,428 kW-months/year |
- - MMBtu |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $1,987 Cost: - |
$1,987 | 33,118 | - | - | - | - | - | - | - | - | - | - |
$1,987 33,118 kWh |
- - kW-months/year |
- - MMBtu |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $1,413 Cost: - |
$712 | 23,740 | $701 | 72 | - | - | - | - | - | - | - | - |
$712 23,740 kWh |
$701 72 kW-months/year |
- - MMBtu |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $1,469 Cost: $1,548 |
- | - | - | - | $1,469 | 288 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$1,469 288 MMBtu |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2122 INSTALL / REPAIR INSULATION ON CONDENSATE LINES |
Savings: $454 Cost: $472 |
- | - | - | - | $454 | 89 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$454 89 MMBtu |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $337 Cost: $286 |
- | - | - | - | $337 | 66 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$337 66 MMBtu |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $169,049 Cost: $168,106 |
$2,699 | 56,858 | $14,610 | 1,500 | $2,260 | 443 | $12,480 | 270,000 | $(-25,000) | - | $162,000 | - | $2,699 56,858 kWh |
$14,610 1,500 kW-months/year |
$2,260 443 MMBtu |
$12,480 270,000 lb |
$(-25,000) - $ |
$162,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $18,156 Cost: $18,106 |
$1,987 | 33,118 | $13,909 | 1,428 | $2,260 | 443 | - | - | - | - | - | - | $1,987 33,118 kWh |
$13,909 1,428 kW-months/year |
$2,260 443 MMBtu |
- - lb |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | lb | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) | Personnel Changes | By-product Production | Electricity Usage | Electricity Demand | Natural Gas | Solid Waste (non-haz) | Personnel Changes | By-product Production |