Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Connecticut |
---|---|
Assessment Year | 2023 |
Principal Product | Industrial joystick controllers |
NAICS | 335314 - Relay and Industrial Control Manufacturing |
SIC | 3625 - Relays And Industrial Controls |
Sales | $10,000,000-$50,000,000 |
# of Employees | 200 |
Plant Area (Sq.Ft.) | 72,000 |
Annual Production | 133,000 Pieces |
Production Hrs. Annual | 2,000 |
Location (State) | CT |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $114,925 | 858,480 | kWh | $0.13 |
Electricity Demand | $56,119 | 4,300 | kW-months/year | $13.05 |
Electricity Fees | $(-5,269) | - | $ | - |
Natural Gas | $26,188 | 1,517 | MMBtu | $17.26 |
TOTAL ENERGY COSTS | $191,962 | |||
RECOMMENDED SAVINGS* | $123,487 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $15,163 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3192 USE FOSSIL FUEL POWERED GENERATOR DURING PEAK DEMAND PERIODS |
Savings: $2,520 Cost: - |
$164 | 1,224 | $355 | 27 | $2,320 | - | $(-319) | (-18) | - | - | - | - |
$164 1,224 kWh |
$355 27 kW-months/year |
$2,320 - $ |
$(-319) (-18) MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $8,636 Cost: $11,635 |
$5,258 | 39,268 | $3,075 | 236 | - | - | - | - | $156 | - | $147 | - |
$5,258 39,268 kWh |
$3,075 236 kW-months/year |
- - $ |
- - MMBtu |
$156 - $ |
$147 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $375 Cost: - |
$112 | 838 | $262 | 20 | - | - | - | - | - | - | - | - |
$112 838 kWh |
$262 20 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $795 Cost: $600 |
$542 | 4,042 | $253 | 19 | - | - | - | - | - | - | - | - |
$542 4,042 kWh |
$253 19 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $1,621 Cost: $1,600 |
$1,105 | 8,250 | $517 | 40 | - | - | - | - | - | - | - | - |
$1,105 8,250 kWh |
$517 40 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $70,539 Cost: $385,242 |
$78,131 | 583,501 | - | - | - | - | - | - | $(-7,592) | - | - | - |
$78,131 583,501 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
$(-7,592) - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $6,153 Cost: $34,274 |
$(-2,603) | (-19,438) | $(-348) | (-27) | - | - | $9,103 | 527 | - | - | - | - |
$(-2,603) (-19,438) kWh |
$(-348) (-27) kW-months/year |
- - $ |
$9,103 527 MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $1,986 Cost: $3,066 |
$180 | 1,348 | - | - | - | - | $1,805 | 105 | - | - | - | - |
$180 1,348 kWh |
- - kW-months/year |
- - $ |
$1,805 105 MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $9,865 Cost: $22,297 |
$8,704 | 65,000 | $1,162 | 89 | - | - | - | - | - | - | - | - |
$8,704 65,000 kWh |
$1,162 89 kW-months/year |
- - $ |
- - MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $207 Cost: $733 |
- | - | - | - | - | - | $207 | 12 | - | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$207 12 MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $429 Cost: $1,916 |
$429 | 3,203 | - | - | - | - | - | - | - | - | - | - |
$429 3,203 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.7234 USE HEAT PUMP FOR SPACE CONDITIONING |
Savings: $20,361 Cost: $73,450 |
$(-7,415) | (-55,380) | $1,585 | 121 | - | - | $26,191 | 1,517 | - | - | - | - |
$(-7,415) (-55,380) kWh |
$1,585 121 kW-months/year |
- - $ |
$26,191 1,517 MMBtu |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $123,487 Cost: $534,813 |
$84,607 | 631,856 | $6,862 | 526 | $2,320 | - | $36,987 | 2,143 | $(-7,436) | - | $147 | - | $84,607 631,856 kWh |
$6,862 526 kW-months/year |
$2,320 - $ |
$36,987 2,143 MMBtu |
$(-7,436) - $ |
$147 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $15,163 Cost: $45,909 |
$2,767 | 20,668 | $2,990 | 229 | - | - | $9,103 | 527 | $156 | - | $147 | - | $2,767 20,668 kWh |
$2,990 229 kW-months/year |
- - $ |
$9,103 527 MMBtu |
$156 - $ |
$147 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Personnel Changes | Ancillary Material Cost |